28
Wiring
Section 2-4
Platinum Resistance
Thermometer
Temperature Control Units
Note
1.
Use the type of sensor selected on the Input Type Switch.
2.
Do not connect anything to the N.C. terminals. (The N.C. terminals cannot
even be used as junction terminals.)
3.
Do not connect any Current Transformer to the CT input terminals other
than an OMRON E54-CT1 or E54-CT3.
4.
Always attach crimp terminals to the wiring that connects to the terminal
block and tighten the terminal screws securely. The terminal screws are
M3 screws and need to be tightened to a torque of 0.5 N
⋅
m.
5.
Use wire that is AWG 22 to AWG 18.
6.
Observe the following precautions when wiring to minimize noise and op-
timize the Temperature Control Unit’s operation.
• Use twisted-pair shielded wire for the output wiring.
• Keep the I/O lines away from power lines including AC power supply
lines and high-power lines. Do not run the I/O lines in the same duct or
conduit as power lines.
CJ1W-TC101
CJ1W-TC102
CJ1W-TC103
CJ1W-TC104
Loo
p 2
CJ1W-TC101
(4 loops, NPN outputs)
CJ1W-TC102
(4 loops, PNP outputs)
CJ1W-TC103
(2 loops, HB alarm, NPN
outputs)
CJ1W-TC104
(2 loops, HB alarm, PNP
outputs)
Lo
op
4
Lo
op 1
Loo
p 3
Lo
op
2
L
oop
4
Loo
p 1
L
oop
3
Loo
p 2
Loo
p 1
Lo
op
2
Lo
op
1
M3
Fork terminal
Round terminal
6.0 mm max.
6.0 mm max.
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......