48
Data Exchange with the CPU Unit
Section 2-5
Operating Parameters
Details
The following table provides details of the Initialization Data settings. For more
details, refer to
2-6 Data Ranges
.
I/O
DM word
Loop
Setting
Description
Output
(CPU
to Tem-
pera-
ture
Con-
trol
Unit)
D (m+10)
Loop 1
Alarm 1 SV
Set in 4-digit BCD or 16-bit binary.
The values written here are written to RAM.
When the BCD data format is being used, the most signifi-
cant digit indicates the sign. (F represents the “
−
” sign.)
D (m+11)
Alarm 2 SV
D (m+12)
Input Compensation Value Set in 4-digit BCD or 16-bit binary.
The values written here are written to RAM.
When the BCD data format is being used, the most signifi-
cant digit indicates the sign. (F represents the “
−
” sign.)
D (m+13)
Control Period
Set in 4-digit BCD or 16-bit binary.
The values written here are written to RAM.
D (m+14)
Control Sensitivity
Set in 4-digit BCD or 16-bit binary.
The values written here are written to RAM.
This setting is valid with ON/OFF control only.
D (m+15)
Proportional Band
Set in 4-digit BCD or 16-bit binary.
The values written here are not written to RAM while the PID
Constants Calculated Flag is ON.
The values written here are written to RAM.
These settings are valid with PID control only
D (m+16)
Integral Time
D (m+17)
Derivative Time
D (m+18)
---
Always set to 0000.
D (m+19)
---
Always set to 0000.
D (m+20)
to
D (m+29)
Loop 2
Same as the settings for
loop 1.
These settings are the same as the settings for loop 1.
(See the description for D (m+10) through D (m+19).)
D (m+50)
to
D (m+59)
Loop 3
Same as the settings for
loop 1.
These settings are valid in Temperature Control Units with
four control loops and are the same as the settings for loop
1.
(See the description for D (m+10) through D (m+19).)
D (m+60)
to
D (m+69)
Loop 4
Same as the settings for
loop 1.
These settings are valid in Temperature Control Units with
four control loops and are the same as the settings for loop
1.
(See the description for D (m+10) through D (m+19).)
Input
(Tem-
pera-
ture
Con-
trol
Unit to
CPU)
D (m+30)
Loop 1
Alarm 1 SV
The Temperature Control Unit returns the values that are
actually being used for temperature control. Use these val-
ues to monitor operation.
D (m+31)
Alarm 2 SV
D (m+32)
Input Compensation Value
D (m+33)
Control Period
D (m+34)
Control Sensitivity
D (m+35)
Proportional Band
D (m+36)
Integral Time
D (m+37)
Derivative Time
D (m+38)
Manipulated variable mon-
itor
Output in 4-digit BCD or 16-bit binary.
When ON/OFF control is being used, this value will be 100%
for ON and 0% for OFF.
D (m+39)
---
Always set to 0000.
D (m+40)
to
D (m+49)
Loop 2
Same as the settings for
loop 1.
These values are the same as the ones for loop 1.
(See the description for D (m+30) through D (m+39).)
D (m+70)
to
D (m+79)
Loop 3
Same as the settings for
loop 1.
These values are valid in Temperature Control Units with
four control loops and are the same as the ones for loop 1.
(See the description for D (m+30) through D (m+39).)
D (m+80)
to
D (m+89)
Loop 4
Same as the settings for
loop 1.
These values are valid in Temperature Control Units with
four control loops and are the same as the ones for loop 1.
(See the description for D (m+30) through D (m+39).)
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......