50
Data Ranges
Section 2-6
Note
1.
If a setting is out-of-range, the Setting Error Flag will be turned ON and the
incorrect setting will be identified by the Setting Error Number. (The incor-
rect setting will be invalid and the Temperature Control Unit will operate
with the previous setting.)
2.
When a loop’s Save Bit is turned ON, that loop’s settings will be saved to
the Temperature Control Unit’s EEPROM.
3.
Do not write the settings to EEPROM more than 100,000 times.
4.
The Heater Burnout Detection function will be disabled if the Heater Burn-
out Current is set to 0.0 A or 50.0 A. The HB Alarm Output will be OFF
when the HB Current is set to 0.0 A; it will be ON when the HB Current is
set to 50.0 A.
2-6-2
Monitored Values
Note
1.
The Manipulated Variable Monitor indicates the manipulated variable that
is presently being output.
When ON/OFF control is being used, this value will be 100% for ON and
0% for OFF.
2.
If the heater current exceeds 55.0 A, the monitor value will indicate CCCC.
Loop 1: D (m+13)
Loop 2: D (m+23)
Loop 3: D (m+53)
Loop 4: D (m+63)
Control
Period
0001 to 0099
0001 to 0063
Sec-
onds
20
The Temperature Con-
trol Unit’s settings are
written to RAM. When
the Save Bit is turned
ON, the settings are
written to EEPROM.
(See notes 2 and 3.)
If DIP switch pin 8 is
ON, the settings are
automatically trans-
ferred from EEPROM
to the CPU Unit when
the power is turned
ON or the Tempera-
ture Control Unit is
restarted.
Loop 1: D (m+14)
Loop 2: D (m+24)
Loop 3: D (m+54)
Loop 4: D (m+64)
Control Sen-
sitivity
0000 to 9999
0000 to 270F
°
C or
°
F
0.8
Loop 1: D (m+15)
Loop 2: D (m+25)
Loop 3: D (m+55)
Loop 4: D (m+65)
Proportional
Band
0001 to 9999
0001 to 270F
°
C or
°
F
8.0
Loop 1: D (m+16)
Loop 2: D (m+26)
Loop 3: D (m+56)
Loop 4: D (m+66)
Integral Time 0000 to 9999
0000 to 270F
Sec-
onds
233
Loop 1: D (m+17)
Loop 2: D (m+27)
Loop 3: D (m+57)
Loop 4: D (m+67)
Derivative
Time
0000 to 9999
0000 to 270F
Sec-
onds
40
Allocated word(s)
Setting
BCD range
Binary range
Units
Default
value
Memory protection
Allocated word
Setting
BCD range
Binary range
Units
Initial
value
Memory
protection
Loop 1: n+3
Loop 2: n+4
Loop 3: n+13
Loop 4: n+14
PV (Process Value)
(Indicates the present
temperature.)
Depend on the input type. Refer to
2-1-3 Input Specifications
.
°
C or
°
F
---
---
Two-loop Tempera-
ture Control Units
only:
Loop 1: n+13
Loop 2: n+14
Heater Current Monitor
0000 to 0550
(See note 2.)
0000 to 0226
(See note 2.)
A
---
---
Loop 1: D (m+18)
Loop 2: D (m+28)
Loop 3: D (m+78)
Loop 4: D (m+88)
Manipulated Variable
Monitor
(See note 1.)
0000 to 1000
0000 to 03E8
%
---
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......