20
Application Procedure
Section 2-2
4.
Mount and wire the Unit, referring to
1-2-2 Mounting the Unit
.
5.
Turn ON the power supply to the PLC.
Creating I/O Tables
There two different methods that can be used to create I/O tables with the CJ-
series PLCs. Refer to the
CJ Series Programmable Controllers Operation
Manual
(W393) for details.
Automation Creation
The PLC can be set to automatically create I/O tables at startup. If this is
done, the user does not need to create the I/O tables.
Use-set I/O Tables
After turning ON the PLC, create the I/O tables. The key sequence for creating
I/O tables from a Programming Console is shown below.
Program
In this example, the process value (PV) output to the words allocated in the
CIO Area to the Temperature Control Unit as a Special I/O Unit are stored in
memory for four loops. The words n+3, n+4, n+13, and n+14 will contain the
PV and are CIO 2013, CIO 2014, CIO 2023, and CIO 2024 in this example.
Note
1.
Determined by the unit number that is set for the Temperature Control Unit
as a Special I/O Unit. (Refer to
2-3-3 Unit Number Switches
.)
2.
Set as desired in programming.
3.
Sensor Error Flags are allocated to bit 14 of n+8, n+9, n+18, and n+19.
(Refer to
Four-loop Units
on page 33.)
Clear
FUN
Shift
CH/*DM
CHG
9
7
1
3
Write
0
or
1
Clear
Input type
Loop
PV address (n = CIO
2010) (See note 1.)
Storage addresses
(See note 2.)
K thermocouple
(0.0 to 500.0
°
C)
1
n+3 = CIO 2013
D00100
2
n+4 = CIO 2014
D00101
3
n+13 = CIO 2023
D00102
4
n+14 = CIO 2024
D00103
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......