63
Using the Heater Burnout Alarm
Section 3-11
3-10-5 Summary of Alarm Output Function Settings
Starting DM Area Word
The starting DM Area word (m) for a Special I/O Unit is calculated as follows:
m = 20000 + (100
×
unit number)
3-11 Using the Heater Burnout Alarm
3-11-1 Heater Burnout Detection
• Follow this procedure to detect heater burnout (an open heating wire).
1,2,3...
1.
Pass the heater wire through the hole in the Current Transformer (CT). Re-
fer to
Current Transformer (CT) Ratings
on page 14 and
Appendix A Di-
mensions
for details on the Current Transformer’s specifications, model
numbers, and dimensions.
2.
When current flows through the heater wire, it induces an AC current in the
Current Transformer (CT) that is proportional to the current in the heater
DM address
Loop
Setting
Data format
Units
Initial
value
Word
Bits
BCD
Binary
D (m+0)
12 to 15
Loop 1
Alarm 1 mode
0 to 9
---
---
0000
08 to 11
Alarm 2 mode
0 to 9
---
04 to 07
Loop 2
Alarm 1 mode
0 to 9
---
00 to 03
Alarm 2 mode
0 to 9
---
D (m+1)
12 to 15
Loop 3
Alarm 1 mode
0 to 9
---
---
0000
08 to 11
Alarm 2 mode
0 to 9
---
04 to 07
Loop 4
Alarm 1 mode
0 to 9
---
00 to 03
Alarm 2 mode
0 to 9
---
D (m+2)
00 to 15
Loop 1
Alarm 1 hysteresis
0000 to 9999
0000 to 270F
°
C or
°
F
0.0
D (m+3)
00 to 15
Alarm 2 hysteresis
0000 to 9999
0000 to 270F
D (m+4)
00 to 15
Loop 2
Alarm 1 hysteresis
0000 to 9999
0000 to 270F
D (m+5)
00 to 15
Alarm 2 hysteresis
0000 to 9999
0000 to 270F
D (m+6)
00 to 15
Loop 3
Alarm 1 hysteresis
0000 to 9999
0000 to 270F
D (m+7)
00 to 15
Alarm 2 hysteresis
0000 to 9999
0000 to 270F
D (m+8)
00 to 15
Loop 4
Alarm 1 hysteresis
0000 to 9999
0000 to 270F
D (m+9)
00 to 15
Alarm 2 hysteresis
0000 to 9999
0000 to 270F
D (m+10)
00 to 15
Loop 1
Alarm 1 SV
F999 to 9999
C3D8 to 3C28
°
C or
°
F
0 or 0.0
D (m+11)
00 to 15
Alarm 2 SV
F999 to 9999
C3D8 to 3C28
D (m+20)
00 to 15
Loop 2
Alarm 1 SV
F999 to 9999
C3D8 to 3C28
°
C or
°
F
0 or 0.0
D (m+21)
00 to 15
Alarm 2 SV
F999 to 9999
C3D8 to 3C28
D (m+50)
00 to 15
Loop 3
Alarm 1 SV
F999 to 9999
C3D8 to 3C28
°
C or
°
F
0 or 0.0
D (m+51)
00 to 15
Alarm 2 SV
F999 to 9999
C3D8 to 3C28
D (m+60)
00 to 15
Loop 4
Alarm 1 SV
F999 to 9999
C3D8 to 3C28
°
C or
°
F
0 or 0.0
D (m+61)
00 to 15
Alarm 2 SV
F999 to 9999
C3D8 to 3C28
Heater wire
To the CT terminals
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......