Data Exchange with the CPU Unit
Section 2-5
Operating Parameters
Contents
The following tables show the specific applications of the bits and words in the
Operating Parameters.
Note
Loops 3 and 4 are applicable to Temperature Control Units with four control
loops only. If a Temperature Control Unit with two control loops is being used,
the settings for loops 3 and 4 will not be used and will be ineffective even if
they are set.
Starting DM Area Word
The starting DM Area word (m) for a Special I/O Unit is:
m = 20000 + (100
×
unit number)
I/O
DM word
Loop
Setting
I/O
DM word
Loop
Setting
Output
(CPU
to Tem-
pera-
ture
Con-
trol
Unit)
D (m+10) Loop 1
Alarm 1 SV
Output
(CPU
to Tem-
pera-
ture
Con-
trol
Unit)
D (m+50) Loop 3
(See
note.)
Alarm 1 SV
D (m+11)
Alarm 2 SV
D (m+51)
Alarm 2 SV
D (m+12)
Input Compensation Value
D (m+52)
Input Compensation Value
D (m+13)
Control Period
D (m+53)
Control Period
D (m+14)
Control Sensitivity
D (m+54)
Control Sensitivity
D (m+15)
Proportional Band
D (m+55)
Proportional Band
D (m+16)
Integral Time
D (m+56)
Integral Time
D (m+17)
Derivative Time
D (m+57)
Derivative Time
D (m+18)
(Not allocated.)
D (m+58)
(Not allocated.)
D (m+19)
(Not allocated.)
D (m+59)
(Not allocated.)
D (m+20) Loop 2
Alarm 1 SV
D (m+60) Loop 4
(See
note.)
Alarm 1 SV
D (m+21)
Alarm 2 SV
D (m+61)
Alarm 2 SV
D (m+22)
Input Compensation Value
D (m+62)
Input Compensation Value
D (m+23)
Control Period
D (m+63)
Control Period
D (m+24)
Control Sensitivity
D (m+64)
Control Sensitivity
D (m+25)
Proportional Band
D (m+65)
Proportional Band
D (m+26)
Integral Time
D (m+66)
Integral Time
D (m+27)
Derivative Time
D (m+67)
Derivative Time
D (m+28)
(Not allocated.)
D (m+68)
(Not allocated.)
D (m+29)
(Not allocated.)
D (m+69)
(Not allocated.)
Input
(Tem-
pera-
ture
Con-
trol
Unit to
CPU)
D (m+30) Loop 1
Alarm 1 SV
Input
(Tem-
pera-
ture
Con-
trol
Unit to
CPU)
D (m+70) Loop 3
(See
note.)
Alarm 1 SV
D (m+31)
Alarm 2 SV
D (m+71)
Alarm 2 SV
D (m+32)
Input Compensation Value
D (m+72)
Input Compensation Value
D (m+33)
Control Period
D (m+73)
Control Period
D (m+34)
Control Sensitivity
D (m+74)
Control Sensitivity
D (m+35)
Proportional Band
D (m+75)
Proportional Band
D (m+36)
Integral Time
D (m+76)
Integral Time
D (m+37)
Derivative Time
D (m+77)
Derivative Time
D (m+38)
Manipulated variable monitor
D (m+78)
Manipulated variable monitor
D (m+39)
(Not allocated.)
D (m+79)
(Not allocated.)
D (m+40) Loop 2
Alarm 1 SV
D (m+80) Loop 4
(See
note.)
Alarm 1 SV
D (m+41)
Alarm 2 SV
D (m+81)
Alarm 2 SV
D (m+42)
Input Compensation Value
D (m+82)
Input Compensation Value
D (m+43)
Control Period
D (m+83)
Control Period
D (m+44)
Control Sensitivity
D (m+84)
Control Sensitivity
D (m+45)
Proportional Band
D (m+85)
Proportional Band
D (m+46)
Integral Time
D (m+86)
Integral Time
D (m+47)
Derivative Time
D (m+87)
Derivative Time
D (m+48)
Manipulated variable monitor
D (m+88)
Manipulated variable monitor
D (m+49)
(Not allocated.)
D (m+89)
(Not allocated.)
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......