34
Data Exchange with the CPU Unit
Section 2-5
Two-loop Units
n = 2000 + (10 x unit number)
I/O
Word
Bit
15
14
13
12
11
10
09
08
07
06
05
04
03
02
01
00
Out-
put
n
Loop 1 Set Point (SP)
n+1
Loop 2 SP
n+2
Loop 1
Loop 2
Loop 1
Loop 2
0
0
0
0
Loop 1
Loop 2
Loop 1
Loop 2
Save
Save
Change
PID
Con-
stants
Change
PID
Con-
stants
0
Stop
0
Stop
Stop AT
Start AT
Stop AT
Start AT
Input
n+3
Loop 1 PV
n+4
Loop 2 PV
n+5
Loop 1 SP
n+6
Loop 2 SP
n+7
Loop 1 Decimal Point
Loop 2 Decimal Point
Loop 1 Setting Error Number
Loop 2 Setting Error Number
n+8
Loop 1 Status
Save
Com-
pleted
Sensor
Error
CT
Over-
flow
Fatal
Control
Error
Stand-
by
PID
Con-
stants
Calcu-
lated
Setting
Error
Stop
0
0
0
Control
Output
AT
HB
AL1
AL2
n+9
Loop 2 Status
Save
Com-
pleted
Sensor
Error
CT
Over-
flow
Fatal
Control
Error
Stand-
by
PID
Con-
stants
Calcu-
lated
Setting
Error
Stop
0
0
0
Control
Output
AT
HB
AL1
AL2
Out-
put
n+10
Heater Burnout Set Value for Loop 1
n+11
Heater Burnout Set Value for Loop 2
n+12
Not used.
Input
n+13
Heater Current for Loop 1
n+14
Heater Current for Loop 2
n+15
Heater Burnout Set Value for Loop 1
n+16
Heater Burnout Set Value for Loop 2
n+17
Not used.
n+18
Not used.
n+19
Not used.
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......