69
Recovering from Sensor Not Connected Errors
Section 4-2
4-2
Recovering from Sensor Not Connected Errors
If a sensor is not connected for any loop, a sensor error will occur and the
ERC indicator on the front panel of the Unit will light. When necessary, the
control and alarm functions for any loop can be disabled. The following status
will result.
• The ERC indicator will not light to indicate sensor errors for the loop.
(Refer to
ERC Indicator Lit and RUN Indicator Lit
on page 73.)
• Control will not be performed for the loop.
• Alarms will not be given for the loop.
• Temperatures will not be input for the loop.
To disable both the control and alarm functions for one or more loops, set the
alarm modes 1 and 2 both to F Hex for each loop to be disabled in the Initial-
ization Data in the DM Area as shown in the following table.
Example:
Set bits 00 to 07 to FF Hex of D (m) to disable loop 2
Note
The above settings are designed to be used to prevent the ERC indicator from
lighting as a result of a sensor error caused by not connecting a sensor for a
loop. If it is necessary to disable only the control function for a loop while leav-
ing the alarm function enabled, set the alarm modes for the loop and then turn
ON the Stop Bit for the same loop.
4-3
Application without a Cycle Refresh with the CPU Unit
Cyclic refreshing of the Temperature Control can be disabled in the cyclic
refresh settings for Special I/O Units in the PLC Setup in the CPU Unit for the
following reasons:
• To shorten the CPU Unit cycle time
• To refresh Operation Data or Operating Parameters using interrupt tasks
or other processing from the ladder program in the CPU Unit.
If cyclic refreshing of Special I/O Units is disabled in the PLC Setup, refresh I/
O for the Unit at least once every 11 seconds using the I/O REFRESH instruc-
tion (IORF), being sure to take into consideration the increase in the cycle
time when IORF is executed.
If the I/O data for the Temperature Control Unit is not refreshed at least every
11 seconds, a CPU Unit monitor error will occur in the Temperature Control
Unit (the ERH and RUN indicators will be lit). Control from the Temperature
Control Unit will continue even if a CPU Unit monitor error occurs.
DM Area
address
Bits
15 14 13 12 11 10 09 08 07 06 05 04 03 02 01 00
D (m)
Loop 1
Loop 2
Alarm mode 1
Alarm mode 2
Alarm mode 1
Alarm mode 2
D (m+1)
Loop 3
Loop 4
Alarm mode 1
Alarm mode 2
Alarm mode 1
Alarm mode 2
Summary of Contents for Sysmac CJ Series
Page 1: ...OPERATION MANUAL Cat No W396 E1 03 SYSMAC CJ Series CJ1W TC Temperature Control Units...
Page 2: ...CJ1W TC Temperature Control Units Operation Manual Revised December 2005...
Page 3: ...iv...
Page 5: ...vi...
Page 13: ...xiv...
Page 23: ......
Page 93: ......
Page 105: ......
Page 107: ......
Page 113: ......
Page 115: ......