Appendix B
Specifications
128
Contact Output Unit C200H-OC224V
Max. Switching Capacity
2 A 250 VAC (cos
f
= 1), 2 A 250 VAC (cos
f
=
0.4), 2 A 24 VDC (16 A/Unit)
Min. Switching Capacity
10 mA 5 VDC
Relay
G6R-1 (24 VDC) w/socket
Service Life of Relay
Electrical: 300,000 operations
Mechanical: 10,000,000 operations
ON Response Time
15 ms max.
OFF Response Time
15 ms max.
No. of Circuits
8 independent contacts
Internal Current Consumption
10 mA 5 VDC max. 90 mA 26 VDC (8 points ON
simultaneously.)
Weight
350 g max.
Dimensions
B-shape
Circuit Configuration
Internal
Circuit
L
Output indicator
250 VAC
24 VDC
max.
OUT
OUTc
Terminal Connections
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
A0
A1
A2
A3
A4
A5
A6
A7
A8
c0
c1
c2
c3
c4
c5
c6
c7
L
L
L
L
L
L
L
L
0
1
2
3
4
5
6
7
250 VAC
24 VDC max.
(inductive load:
2 A resistive
load: 2 A)
(16 A/Unit)
NC
NC
NC