Appendix B
Specifications
140
Terminal Connections
+24 VDC
24 VDC
C200HS-INT01 Interrupt Input Unit
The Interrupt Input Unit temporarily interrupts the main program by means of in-
puts, and executes interrupt subroutines. It must be mounted to a C200HS CPU
Rack, and there can be only one Interrupt Input Unit on the Rack. (It is possible to
mount it to an Expansion I/O Rack, but in that case it will be treated as a Standard
Input Unit and will have no interrupt functions.) Use a C200H-BC
jj
1-V2 Back-
plane. The word number of the slot position to which the Unit is mounted is allo-
cated as eight input points.
Operation display area:
Displays the ON/OFF status of interrupts.
Terminal block:
Consists of removable components.
Rated Input Voltage
12 to 24 VDC
+10%
/
–15%
Input Impedance
2 K
Ω
Input Current
10 mA typical (24 VDC)
ON Voltage
10.2 VDC min.
OFF Voltage
3.0 VDC max.
ON Response Time
0.2 ms max.
OFF Response Time
0.5 ms max.
No. of Circuits
1 (8 points/common)
Internal Current Consumption
20 mA, 5 VDC max.
Weight
200 g max.