103
Appendix B
Specifications
The following figures and tables provide specifications for each Unit of the C200HS. I/O Units may take on one of
three different shapes and are sometimes referred to as A-shape Units, B-shape Units, or E-shape Units. Group-2
High-density I/O Units take on one of two different shapes and are sometimes referred to as C-shape Units or
D-shape Units. Refer to the figures at the end of the I/O Unit specifications for the exact dimensions of these five
shapes of I/O Unit.
CPUs and Power Supplies
General Specifications
Item
C200HS-CPU01-E/CPU01-EC/CPU21-E/
CPU21-EC/CPU31-E,
C200H-PS221/PS221-C
C200HS-CPU03-E/CPU23-E/
CPU33-E, C200H-PS211
Supply Voltage
100 to 120/200 to 240 VAC selectable
50/60 Hz
24 VDC
Operating Voltage Range
85 to 132/170 to 264 VAC
20.4 to 26.4 VDC
Power Consumption
120 VA max.
40 W max.
Surge Current
30 A max.
30 A max.
Output Capacity
CPU01-E/CPU01-EC/CPU21-E/CPU21-EC/CPU31-E:
4.6 A, 5 VDC (3.9 A supplied to I/O Units)
CPU03-E/CPU23-E/CPU33-E: 3 A, 5 VDC (2.3 A supplied to I/O Units)
Expansion I/O Rack: 3 A, 5 VDC (2.7 A supplied to I/O Units)
Fuse
2 A 250 V 5.2 dia. x 20 (MF51NR)
2 A 125 V 5.2 dia. x 20 (MF51NR)
24 VDC Output
0.3 A, 24 VDC
+10%
/
–20%
None
Insulation Resistance
20 M
Ω
between AC terminals and the GR
terminal at 500 VDC (See note 1.)
(See note 2.)
Dielectric Strength
2,300 VAC at 50/60 Hz for 1 minute
between AC terminals and housing;
1,000 VAC at 50/60 Hz for 1 minute
between DC terminals and housing.
Leakage current: 10 mA max. (See note 1.)
(See note 2.)
Noise Immunity
1,500 Vp-p, pulse width: 100 ns to 1
µ
s, rise time: 1 ns pulse (by noise simulator)
Vibration
JIS C0911 conforming,10 to 57 Hz; 0.075 mm amplitude, 57 to 150 Hz; acceleration:
9.8 m/s
2
(see note 3), in X, Y, and Z directions, for 80 minutes each (sweep time 8 min x
10 sweeps = 80 min); (When mounted on DIN track, 2 to 55 Hz, 2.94 m/s
2
, in X, Y, and Z
directions, for 20 minutes each)
Shock
JIS C0912 conforming, 147 m/s
2
in X, Y, and Z directions, 3 times each
Ambient Temperature
Operating: 0
°
to 55
°
C; storage: –20
°
to 75
°
C (without battery)
Humidity
10% to 90% (without condensation)
Atmosphere
Must be free of the following:
•
Corrosive gases
•
Abrupt temperature changes
•
Direct sunlight
•
Dust, salt, or metal filings
•
Water, oil, or chemicals
Grounding
Connect to a ground of 100
Ω
or less
Enclosure Rating
Mounted in a panel
Weight
6 kg max.
Note
1. Internal components might be damaged if insulation resistance or dielectric strength tests are con-
ducted with the LG and GR terminals connected.
2. Do not conduct a dielectric strength test on the C200HS-CPU03-E/CPU23-E/CPU33-E, PS211,
RT002-P, or RT202 Units. The power supply input line and internal circuit of the 24 VDC Power Supply
Summary of Contents for SYSMAC C200H
Page 1: ...Cat No W236 E1 07 INSTALLATION GUIDE SYSMAC C200HS Programmable Controllers ...
Page 2: ......
Page 3: ...C200HS Programmable Controllers Installation Guide Revised March 2003 ...
Page 6: ...vi ...
Page 10: ...x ...
Page 28: ......
Page 46: ......
Page 74: ......
Page 98: ......
Page 106: ......
Page 218: ......
Page 226: ......
Page 228: ......
Page 229: ......
Page 230: ...W236 E1 07 ...