Appendix B
Specifications
175
Analog Timer Unit C200H-TM001
Item
Specifications
Oscillation Method
CR oscillation
Time Setting Range
Use the DIP switch to set any of the following four ranges, according to the chart shown on
the next page.
0.1 to 1 second (typical)
1 to 10 seconds (typical)
10 to 60 seconds (typical)
1 to 10 minutes (typical)
Timer Pause Function
The timing operation can be paused if so specified by the program. Therefore, the timers can
also be used as cumulative registers.
Number of Timer Points
4
Indicators
SET and TIME UP
External Variable
Resistor
External variable resistors can be used to set the time value when the IN/EXT selector is set
to OFF (EXT). Use 20 k
W
variable resistors.
Bit Allocation
Function
T0 start output
T1 start output
T2 start output
T3 start output
T0 pause output
T1 pause output
T2 pause output
T3 pause output
T0 time-up input
T1 time-up input
T2 time-up input
T3 time-up input
Cannot be used
Bit
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
“1” when time is running
0
1
Operates
Stops
“1” when time is up
The word is determined by the system configuration.
Programming and
Timing Chart
Timer start input
word n bits 08 through 11
Time-up flag
Time-up output
Timer setting
(word n bits 00
through 03)
Timer start
input
Time-up
output
Timer set value
Internal Current
Consumption
60 mA 5 VDC max.
Summary of Contents for SYSMAC C200H
Page 1: ...Cat No W236 E1 07 INSTALLATION GUIDE SYSMAC C200HS Programmable Controllers ...
Page 2: ......
Page 3: ...C200HS Programmable Controllers Installation Guide Revised March 2003 ...
Page 6: ...vi ...
Page 10: ...x ...
Page 28: ......
Page 46: ......
Page 74: ......
Page 98: ......
Page 106: ......
Page 218: ......
Page 226: ......
Page 228: ......
Page 229: ......
Page 230: ...W236 E1 07 ...