Appendix B
Specifications
146
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in
each connector. Connect power supply wiring to every COM terminal, even though the COM terminals in
each connector are connected internally.
DC Input Unit C200H-ID218
Rated Input Voltage
24 VDC
+10%
/
–15%
Input Impedance
3.9 k
Ω
Input Current
6 mA (at 24 VDC)
ON Voltage/ON Current
15.4 VDC min./3.5 mA min.
OFF Voltage/OFF Current
5.0 VDC max./1 mA max.
ON Response Time
1.0 ms max.
OFF Response Time
1.0 ms max.
No. of Circuits
32 (32 points/common)
Note
The number of points that can be ON simulta-
neously is limited according to the ambient
temperature. Refer to the following diagram
for details.
Internal Current Consumption
100 mA 5 VDC max.
Weight
180 g max.
Circuit Configuration
to
to
to
to
0.01
µ
F
470
Ω
3.9 k
Ω
0.01
µ
F
470
Ω
3.9 k
Ω
Input LED indicator
Internal circuit
Input LED indicator
Simultaneously ON points
Ambient Temperature for Simultaneously ON Points
Input voltage: 24.0 VDC
Input voltage: 26.4 VDC
Ambient temperature
Summary of Contents for SYSMAC C200H
Page 1: ...Cat No W236 E1 07 INSTALLATION GUIDE SYSMAC C200HS Programmable Controllers ...
Page 2: ......
Page 3: ...C200HS Programmable Controllers Installation Guide Revised March 2003 ...
Page 6: ...vi ...
Page 10: ...x ...
Page 28: ......
Page 46: ......
Page 74: ......
Page 98: ......
Page 106: ......
Page 218: ......
Page 226: ......
Page 228: ......
Page 229: ......
Page 230: ...W236 E1 07 ...