Appendix B
Specifications
143
2. The power can be supplied in either polarity, but the same polarity must be used for all COM terminals in
each connector. Connect power supply wiring to every COM terminal, even though the COM terminals in
each connector are connected internally.
DC Input Unit C200H-ID216 (32 Points)
Rated Input Voltage
24 VDC
Operating Input Voltage
20.4 to 26.4 VDC
Input Impedance
5.6 k
W
Input Current
4.1 mA (at 24 VDC)
ON Voltage
14.4 VDC min.
OFF Voltage
5.0 VDC max.
ON Response Time
1.0 ms max.
OFF Response Time
1.0 ms max.
No. of Circuits
1 (32 points/common)
All 32 points cannot be turned ON simultaneously
at high temperatures. Refer to the following graph.
Internal Current Consumption
100 mA 5 VDC max.
Weight
180 g max.
Dimensions
C-shape
Circuit Configuration and Simultaneously Usable Points
Input indicator
Input indicator
Input Voltage: 26.4 VDC
Ambient Temperature (
°
C)
Simultaneously Usable Points
0
10
20
30
40
50 55 60
0
5
10
15
20
25
30
32
1000 pF
680
W
5.6 k
W
COM
IN00
IN07
COM
IN08
IN15
A
Internal
Circuit
COM
IN00
IN07
COM
IN08
IN15
B
1000 pF
680
W
5.6 k
W
Summary of Contents for SYSMAC C200H
Page 1: ...Cat No W236 E1 07 INSTALLATION GUIDE SYSMAC C200HS Programmable Controllers ...
Page 2: ......
Page 3: ...C200HS Programmable Controllers Installation Guide Revised March 2003 ...
Page 6: ...vi ...
Page 10: ...x ...
Page 28: ......
Page 46: ......
Page 74: ......
Page 98: ......
Page 106: ......
Page 218: ......
Page 226: ......
Page 228: ......
Page 229: ......
Page 230: ...W236 E1 07 ...