Appendix B
Specifications
106
Standard I/O Units
AC Input Unit C200H-IA121
Rated Input Voltage
100 to 120 VAC 50/60 Hz
Operating Input Voltage
85 to 132 VAC 50/60 Hz
Input Impedance
9.7 k
W
(50 Hz), 8 k
W
(60 Hz)
Input Current
10 mA typical (at 100 VAC)
ON Voltage
60 VAC min.
OFF Voltage
20 VAC max.
ON Response Time
35 ms max. (at 100 VAC, 25
°
C)
OFF Response Time
55 ms max. (at 100 VAC, 25
°
C)
No. of Circuits
1 (8 points/common)
Internal Current Consumption
10 mA 5 VDC max.
Weight
250 g max.
Dimensions
A-shape
Circuit Configuration
IN
IN
COM
Internal
Circuit
100 to
120 VAC
470
W
Input indicator
0.33
m
F
330 k
W
910
W
Terminal Connections
COM
A0
A1
A2
A3
A4
A5
A6
A7
A8
A9
0
1
2
3
4
5
6
7
NC
100 to
120 VAC