78
Error and message
Possible correction
Probable cause
FAL no.
Interrupt subroutine error
SYS FAIL FAL8B
8B
Interrupt subroutine
containing Special I/O Unit
refresh was too long.
Cyclic Special I/O Unit
refreshing was not disabled
for interrupt subroutine
refresh.
Check the interrupt
subroutine and PC Setup.
High-density I/O Unit error
SYS FAIL FAL9A
9A
An error occurred in data
transfer between a
High-density I/O Unit and
the CPU.
Check AR 0205 to AR 0214
to identify the Unit with a
problem, replace the Unit,
and restart the PC.
PC Setup error
SYS FAIL FAL9B
9B
An error has been detected
in the PC Setup. This error
will be generated when the
setting is read or used for
the first time.
Check an correct PC Setup
settings.
Memory Cassette Transfer error
SYS FAIL FAL9D
9D
An error has occurred
during data transmission
between UM and a Memory
Cassette because:
Not in PROGRAM Mode.
UM or Memory Cassette is
read-only.
Insufficient capacity in UM
or Memory Cassette.
A checksum error occurred
in the Memory Cassette
Make sure that the PC is in
PROGRAM mode.
Make sure that the Memory
Cassette is not
write-protected.
Make sure that the UM and
Memory Cassette capacity
is sufficient.
Make sure the SYSMAC
NET data link is not
operating and transfer again
(SR 27011 will be ON).
Transfer the data again.
Cycle time overrun
CYCLE TIME OVER
F8
Watchdog timer has
exceeded 100 ms.
Program cycle time is
longer than recommended.
Reduce cycle time if
possible.
I/O table verification error
I/O VER ERR
E7
Unit has been removed or
replaced by a different kind
of Unit, making I/O table
incorrect.
Use I/O Table Verify
Operation to check I/O table
and either connect dummy
Units or register the I/O
table again.
REMOTE ERR
Remote I/O error
*
Remote I/O
Master Unit number
B0 or B1
Error occurred in
transmissions between
Remote I/O Units.
Check transmission line
between PC and Master
and between Remote I/O
Units.
SIOU ERR
Special I/O Unit error
D0
Error has occurred in PC
Link Unit, Remote I/O
Master Unit, between a
Host Link, SYSMAC LINK,
or SYSMAC NET Link Unit
and the CPU, or in refresh
between Special I/O Unit
and the CPU.
Determine the unit number
of the Unit which caused the
error (AR 00), correct the
error, and toggle the
appropriate Restart Bit in
AR 01, SR 250, or SR 252.
If the Unit does not restart,
replace it.
Battery error
BATT LOW
F7
Backup battery is missing or
its voltage has dropped.
Check battery, and replace
if necessary.
Error Messages
Section 6-4
Summary of Contents for SYSMAC C200H
Page 1: ...Cat No W236 E1 07 INSTALLATION GUIDE SYSMAC C200HS Programmable Controllers ...
Page 2: ......
Page 3: ...C200HS Programmable Controllers Installation Guide Revised March 2003 ...
Page 6: ...vi ...
Page 10: ...x ...
Page 28: ......
Page 46: ......
Page 74: ......
Page 98: ......
Page 106: ......
Page 218: ......
Page 226: ......
Page 228: ......
Page 229: ......
Page 230: ...W236 E1 07 ...