Appendix B
Specifications
118
Triac Output Unit C200H-OA222V
Max. Switching Capacity
0.3 A 250 VAC, 50/60 Hz (2 A/Unit)
Min. Switching Capacity
10 mA (resistive load)/40 mA (inductive load)
10 VAC
Leakage Current
3 mA (100 VAC) max./6 mA (200 VAC) max.
Residual Voltage
1.2 V max.
ON Response Time
1/2 of load frequency or less.
OFF Response Time
1/2 of load frequency or less.
No. of Circuits
1 (12 points/common)
Internal Current Consumption
200 mA 5 VDC max.
Fuse Rating
3 A 250 V (5.2-dia.x20)
Power for External Supply
N/A
Weight
400 g max.
Dimensions
B-shape
Circuit Configuration
L
Internal
Circuit
OUT
COM
OUT
Output indicator
L
250 VAC max.
Fuse: 3 A 250 V (5.2-dia.x20) MQ4 (SOC)
Fuse
Note
1. No blown fuse detector circuit is provided.
2. Check the fuse when there is no output.
Terminal Connections
A0
A1
A2
A3
A4
A5
A6
A7
A8
B0
B1
B2
B3
B4
B5
B6
B7
B8
B9
COM
1
3
5
7
9
11
NC
0
2
4
6
8
10
NC
NC
NC
NC
250 VAC max.
(0.3 A max., 2 A/Unit)
L
L
L
L
L
L
L
L
L
L
L
L
NC
Summary of Contents for SYSMAC C200H
Page 1: ...Cat No W236 E1 07 INSTALLATION GUIDE SYSMAC C200HS Programmable Controllers ...
Page 2: ......
Page 3: ...C200HS Programmable Controllers Installation Guide Revised March 2003 ...
Page 6: ...vi ...
Page 10: ...x ...
Page 28: ......
Page 46: ......
Page 74: ......
Page 98: ......
Page 106: ......
Page 218: ......
Page 226: ......
Page 228: ......
Page 229: ......
Page 230: ...W236 E1 07 ...