5-5 Operating Functions
5-5-1 Brake Interlock
5-10
RUN Command Timing (When Servomotor Is Rotating)
RUN
(Run command)
BKIR
(brake interlock)
Servomotor power
Servomotor speed
Energized
Not
energized
(See note 2.)
(See note 1.)
ALM
(alarm output)
Note 1. The Servomotor will continue to rotate due to its momentum for about 15 ms after the
Servomotor de-energizes until the dynamic brake operates.
2. The BKIR (brake interlock) signal will be turned OFF if the Servomotor rotation speed
falls below 100 r/min or 500 ms has elapsed since the Servo went OFF.