269
Areas for Control/Notification
Section 7-2
Reference
- What is designated here is the memory table number only. The type of memory
table (numeral/character string) is set by the “memory table copy type” bit in the
PT status control bits.
- Copying is not executed just be writing the memory table numbers. It is execut-
ed when the “memory table copy execution” bit in the PT status control bits is
turned ON.
- Since the memory table numbers start from 0, if there are 2000 memory tables,
the range is 0 to 1999, and if there are 1000, the range is 0 to 999.
S
PT status control bits
The PT status control bits have the functions indicated below.
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Bit
0
0
Controlled Item
Screen display
Processing priority registration (for NT link (1:N))
Continuous buzzer
Intermittent buzzer (short)
Display history initialization
Not used
Intermittent buzzer (long)
Backlight mode
Screen printing
PT window opening
Numeral/character string input
PT screen switching
Memory table copy execution
Memory table copy type
Alarm history initialization
Not used
1 (ON)
Performed
Registered
Sounded
Sounded
Performed
Sounded
Lit
Performed
Disabled
Disabled
Disabled
Performed
Numeral
Performed
0 (OFF)
Not performed
Canceled
Stopped
Stopped
Not performed
Stopped
Flashing
Not performed
Enabled
Enabled
Enabled
Not performed
Character string
Not performed
Always “0”
Always “0”
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
n+3ch
Reference
- Since the statuses of the PT status control bits do not change even if the status
of the NT31/NT31C changes in accordance with the settings of attributes or
memory switches, the statuses of the PT status control bits may sometimes dis-
agree with the status of the NT31/NT31C. For example, the buzzer may be
sounding even though the “continuous buzzer” bit is OFF. In such a case, per-
form PT status control bit operations to achieve agreement with the status of the
NT31/NT31C.
- The PT status control bits are checked in bit units by the NT31/NT31C. The only
functions that are actually performed are those for which the corresponding bits
have changed in status.
Summary of Contents for NT31 Series
Page 1: ...Cat No V043 E1 2 Programmable Terminal NT31 31C OPERATION MANUAL...
Page 2: ...iii NT31 31C Programmable Terminal Operation Manual Produced March 1999...
Page 41: ...30 Before Operating Section 1 5...
Page 75: ...64 Using a Memory Unit NT31 NT31C without V1 Section 3 6...
Page 160: ...149...
Page 174: ...163...
Page 193: ...182...
Page 211: ...200...
Page 235: ...224 c Return to the screen on which screens are specified...
Page 262: ...251...
Page 360: ...349 It is not possible to control a gloval window by touch switch operation...
Page 468: ...457 254 255 0 2 7 1 4 5 3 3 0 0 0 5 9 8 0 3...
Page 476: ...465 Special Functions Section 7 16...
Page 495: ...484 OFF...
Page 610: ...599 Commands Responses Section 9 3...
Page 630: ...619 Examples of Actual Applications of Memory Link Section 10 2...