267
Areas for Control/Notification
Section 7-2
[Screen switch setting in the PT status control area]
15 14 13 12 11 10 9
8
7
6
5
4
3
2
1
0
Word
Bit
n
Screen switch setting
Screen number (4-digit BCD or hexadecimal)
The screen numbers that can be set are as follows.
BCD
Hexadecimal
Screen
0000
H
0000
H
No-display (screen cleared)
0001 to 3999
H
0001 to 0F9F
H
(3999)
Screen numbers 1 to 3999
9001
H
2329
H
(9001)
Occurrence history screen
9002
H
232A
H
(9002)
Frequency history screen
Reference
- The screen can also be switched by bit memory table operation (page 480), by
touch switch operation (page 481), or by using the alarm list/history function
(page 485).
- To display overlapping screens, designate the screen number of the parent
screen.
- If there are no elements registered for the designated screen number, or if a key-
board screen is designated, the screen does not switch.
- When the NT31/NT31C starts operating, the screen is displayed according to
the contents of the “screen switch setting” word. If the contents of the “screen
switch setting” word are invalid, the screen is displayed according to the “Initial
Screen” in the PT configuration settings made at the Support Tool. If the setting
for “Initial Screen” is also invalid, an error message is displayed.
- When data is written from the NT31/NT31C
When the screen display has been switched by operation at the NT31/NT31C,
the new screen number is written as a 4-digit BCD or hexadecimal value into
the “screen switch setting” word by the NT31/NT31C. At the same time, the
“ON” status is also notified to the screen switch strobe flag of the “PT status”
word of the PT status notify area by the NT31/NT31C (after notification, the
OFF status is re-established) (page 487). Whether the data is written in BCD
or hexadecimal format is determined by the setting for “numeral storage type”
in the PT configuration settings made at the Support Tool.
Currently displayed
screen
PC
NT31/NT31C
←
Screen number
PT status control area
Screen switch setting
Copy memory
table setting
PT status control setting
Reserved for system use
←
Screen switch strobe flag
PT status notify area
Content update memory table
PT status
Summary of Contents for NT31 Series
Page 1: ...Cat No V043 E1 2 Programmable Terminal NT31 31C OPERATION MANUAL...
Page 2: ...iii NT31 31C Programmable Terminal Operation Manual Produced March 1999...
Page 41: ...30 Before Operating Section 1 5...
Page 75: ...64 Using a Memory Unit NT31 NT31C without V1 Section 3 6...
Page 160: ...149...
Page 174: ...163...
Page 193: ...182...
Page 211: ...200...
Page 235: ...224 c Return to the screen on which screens are specified...
Page 262: ...251...
Page 360: ...349 It is not possible to control a gloval window by touch switch operation...
Page 468: ...457 254 255 0 2 7 1 4 5 3 3 0 0 0 5 9 8 0 3...
Page 476: ...465 Special Functions Section 7 16...
Page 495: ...484 OFF...
Page 610: ...599 Commands Responses Section 9 3...
Page 630: ...619 Examples of Actual Applications of Memory Link Section 10 2...