background image

TECHNICAL NOTE

Page Rev.

Date

Issued

Approved

37

1

0

05/09/16

DBC.4

“increased

safety”

terminal

blocks,

are

manufactured

according

to

the

prescriptions

given

by

IEC / EN 60079-0, IEC / EN 60079-7 Standards and are in compliance with the ATEX 2014/34/UE Directive and the
IEC Ex Certification Scheme
DBC.4 terminal blocks are also designed and manufactured in compliance with IEC / EN 60947-1 and IEC / EN 60947-7-1
reference product standards.
Terminal blocks (components) must be inserted in Ex e enclosures. The terminal  enclosure assembly must
be subjected to separate certification.
DBC.4 terminal blocks are suited for a temperature range between - 40 and + 80 °C
Ambient temperature range shall be between - 40 and + 40 °C

Rail assembly composition in potentially explosive (Ex e) environments

End section

Comb-type cross connection PTC “Easy bridge”

Mounting rail

End bracket

Each rail assembly is formed by two or more adjoining terminal blocks and by END BRACKETS, that are located at the ends of
the assembly, in a way to obtain a compact and single arrangement.
As the back of each terminal block performs the function of insulating wall for the adjoining terminal block, an END SECTION is
necessary to close and provide appropriate insulation to the first terminal block forming the assembly.
Rail assemblies can be subdivided into groups by interposing COLOURED PARTITIONS, in order to ease the location of
different circuits
Each terminal block can be connected to adjoining elements by means of CROSS CONNECTION of the comb type.
Adjoining terminal blocks can be visually separated by interposing a COLOURED PARTITION, having a thickness of 1,5 mm.
Adjoining jumpers between different phases should be electrically separated by interposing an END SECTION type DBC/PT.
Multiple cross connections can be performed between terminal blocks, by means of a comb-type CROSS CONNECTION the
use of which enables also to obtain parallel extending, pole skipping, staggered, and parallel skipping cross-connection
schemes

Ex e Instruction Manual N° 37

Summary of Contents for DBC.4

Page 1: ...ining terminal blocks and by END BRACKETS that are located at the ends of the assembly in a way to obtain a compact and single arrangement As the back of each terminal block performs the function of insulating wall for the adjoining terminal block an END SECTION is necessary to close and provide appropriate insulation to the first terminal block forming the assembly Rail assemblies can be subdivid...

Page 2: ...l skipping Ex e rated voltage Vac Ex e rated voltage Vac Ex e rated voltage Vac Ex e rated voltage Vac Ex e rated voltage Vac DBC 4 upper level 250 250 250 250 250 DBC 4 lower level 250 250 250 250 250 Notes rated voltage values can be subjected to a 10 tolerance as listed in Table 1 of IEC 60079 7 Std TERMINAL BLOCK JUMPER MULTIPLE COMMONING BAR SCREW AND SLEEVE CURRENT OF THE JUMPER A DBC 4 PTC ...

Page 3: ...ks to their coupling it is possible to apply the correct contact pressure By acting on the tightening screw the collar tightens the conductor against the conducting body which is manufactured in tin plated copper With the clamping yoke tightening system a gas proof particularly safe connection is guaranteed Thanks to the force applied during the tightening process the overlapped threaded parts sys...

Page 4: ...body the name of the product and the electrical characteristics ATEX Marking 0722 I M 2 Ex eb I Mb II 2G Ex eb IIC Gb 0722 number of Notifying Body CESI for the ATEX surveillance I M2 group I mines category M2 II 2 G group II surface category 2 G gas Ex eb increased safety protection mode IIC gas group Gb EPL I group I mines Mb EPL V rated voltage The CE Marking indicates the Conformity to EU Low ...

Reviews: