90
6-2
Output Test
This function is convenient for checking a system to which the K3NP is con-
nected, especially when some inputs cannot be operated. The K3NP simulates
an input signal to check the output conditions.
Note
The K3NP has output according to the simulated input in this menu. If there is
any device connected to the output of the K3NP, be sure that the output will not
have a negative influence on the device before testing the system.
·
Follow the steps described below to perform the test.
1, 2, 3...
1. While the K3NP is in RUN mode, press the Escape Key for more than one
second to set the K3NP to the setting mode.
2. Repeatedly press the Mode Key until the
test
output test setting is dis-
played.
RUN mode
Setting Mode
1 second
Setting values menu
Prescaling menu
Output Test
Option menu
Setup menu
sUset
test
opt
setup
pscl
3. Press the Mode Key for more than one second to display 0, which is a simu-
lated input value.
4. The simulated input value increases when the Up Key is pressed. Compara-
tive outputs are output according to the output pattern that has been preset.
5. The simulated input value decreases when the Shift Key is pressed. Com-
parative outputs are output according to the output pattern that has been
preset.
6. Press the Escape Key after testing. The
test
output test setting will be dis-
played again.
7. Press the Escape Key to return to the RUN mode.
·
To change the simulated input value continuously, keep pressing the Up or
Shift Key.
Output Test
Section 6-2
Summary of Contents for K3NP
Page 1: ...K3NP Period Meter Operation Manual Produced January 1998...
Page 2: ...iv...
Page 4: ...vi...