![background image](http://html1.mh-extra.com/html/omron/k3np/k3np_operation-manual_743364065.webp)
56
Communications Unit Number
Baud Rate
·
Set a communications unit number as an identification number by which the
host computer is connected to the K3NP.
·
If more than one K3NP is connected in parallel, make sure that each commu-
nications unit number is unique.
·
The baud rate should be set to the baud rate of the host computer.
·
Communications Unit Number
Setting range
Unit
Default
00 to 99
---
00
·
Baud Rate
Setting range
Default
1200
: 1,200 bps /
2400
: 2,400 bps /
4800
: 4,800 bps /
9600
: 9,600 bps /
19200
:19.2 Kbps /
38400
: 38.4 Kbps
9600
This setting is available for the K3NP with the Communications Output Board.
Follow the steps described below to set the communications unit number to 15 and the
baud rate to 19,200 bps.
Set Value LED Display Model
Basic Model
1, 2, 3...
1. Press the Mode Key for more than one second while the
setup
setup menu
is displayed. The
func
operating mode setting will appear.
Set Value LED Display Model
Basic Model
2. Repeatedly press the Mode Key until the
u-no
communications unit number
setting is displayed.
Set Value LED Display Model
Basic Model
u-no
bps
FUNCTION
SETTING
MODELS
SETTING
EXAMPLE
Setting Mode
Section 4-2
Summary of Contents for K3NP