Appendices
Appendices
A-16
*3 Variable C0 is used for reading communications data.
*4 Set the “bank” parameter to “EV” when an event input (connector) is mounted as a standard feature or
has been added.
Advanced
function
settings
Set value initialization
init
OFF, ON
off
,
on
OFF
---
---
Output OFF delay
off-d
0 to 1999
0
to
1999
0
---
ms
Shot output
shot
0 to 1999
0
to
1999
0
---
ms
Output logic
out-n
Close in alarm, open in
alarm
n-o
,
n-c
Close in alarm
---
---
Bank selection
bnk-c
OFF, KEY, EV
off
,
key
,
ev
OFF*
---
---
Others
Linear output
calibration value H
---
---
---
---
---
---
Linear output
calibration value L
---
---
---
---
---
---
Level
Parameter name
Characters
Setting range
Characters
Initial value
Decimal point
Unit
Set
value