Initial Setup
Section 4 Initial Setup
4-4
4.2 Initial Setup Example for the K3HB-P
The initial setup is explained in the following example.
Settings Example
The passing speed is displayed in m/s when the distance between A
and B is 5 m.
• If the measurement value goes above 0.700, comparative output
H turns ON.
• If the measurement value goes below 0.500, comparative output L
turns ON.
Setting the Prescale Value
The prescale value can be obtained using the following formula when
the output is to be displayed in m/s.
Prescale value (
α
) = 5/60 = 0.08333 ... = 8.3333
×
10
−
2
Prescale value of Input A, X (mantissa):
ps.
ax
=
8.
3333
Prescale value of Input B, Y (exponent):
ps.
ay
=
10 -2
Initial Setup Flow
●
To change a set value, press the
S
[SHIFT] Key once to enable
changing the setting and then press the
U
[UP] Key to change the
value.
Press the
M
[MODE] Key to register the set value. The set value will
be registered and the next parameter will be displayed.
• The display will show “-----”.
1. Move to the initial setting level by pressing the
L
[LEVEL] Key for at least
3 s (operation will stop).
2. Set “
func
” to “
f1
” and press the
M
[MODE] Key.
1. Set input type A “
in-ta
” to “
00
” and press the
M
[MODE] Key.
2. Set input type B “
in-ta
” to “
00
” and press the
M
[MODE] Key.
A
Check the wiring and turn the power ON.
B
Set the function to F1 (passing speed).
C
Set input type A and input type B to 00 (no-contact, normally
open).
0.500
0.700
Comparative output H
Comparative output L
Measurement
value
A
K3HB-P
B
Summary of Contents for K35-2
Page 2: ......
Page 24: ...Outline Section 1 Outline 1 8 ...
Page 25: ...2 1 Preparations Section 2 Preparations 2 1 Mounting 2 2 2 2 Using I O 2 4 ...
Page 54: ...Basic Application Methods Basic Application Methods Section 3 Basic Application Methods 3 18 ...
Page 62: ...Initial Setup Section 4 Initial Setup 4 8 ...
Page 148: ...Functions and Operations Section 5 Functions and Operations 5 86 ...
Page 149: ...6 1 Troubleshooting Section 6 Troubleshooting 6 1 Error Displays 6 2 6 2 Countermeasures 6 3 ...
Page 152: ...Troubleshooting Section 6 Troubleshooting 6 4 ...
Page 185: ......