Basic Application MethodsBasic Application Methods
3.6 Measuring the Feed Length of a Sheet: K3HB-C
3-13
3.6 Measuring the Feed Length of a Sheet: K3HB-C
Advantages of using the K3HB-C
• Displays the measurement value to tenths of a millimeter (0000.0
mm) using a rotary encoder that outputs 250 pulses to measure a
feed length of 0.5 m.
• Outputs comparative output OUT1 when the measurement value
is 500.0 or higher.
• Outputs comparative output OUT2 when the measurement value
is 700.0 or higher.
700.0
500.0
0.5 m
K3HB-C
K3HB-C
A B C D
E
1
2
3
4
5
6
E6B2-CWZ6C
COM
+
250 pulses
Encoder
Comparative output OUT2
Comparative output OUT1
Connections Diagram
Operating power
Phase
B
Phase
A
Measurement value
100 to 240 VAC
24 VDC/AC
Summary of Contents for K35-2
Page 2: ......
Page 24: ...Outline Section 1 Outline 1 8 ...
Page 25: ...2 1 Preparations Section 2 Preparations 2 1 Mounting 2 2 2 2 Using I O 2 4 ...
Page 54: ...Basic Application Methods Basic Application Methods Section 3 Basic Application Methods 3 18 ...
Page 62: ...Initial Setup Section 4 Initial Setup 4 8 ...
Page 148: ...Functions and Operations Section 5 Functions and Operations 5 86 ...
Page 149: ...6 1 Troubleshooting Section 6 Troubleshooting 6 1 Error Displays 6 2 6 2 Countermeasures 6 3 ...
Page 152: ...Troubleshooting Section 6 Troubleshooting 6 4 ...
Page 185: ......