Functions and Oper
ations
Section 5 Functions and Operations
5-20
■
F5: Measuring Length
Measuring workpiece length
•
Basic operation
Displays the number of input A pulses while input B is ON.
The measurement value can be obtained using the following
formula:
D
=
C
×
α
C
: Number of pulses of input A while input B is ON
α
: Prescale value A
D
: Measured length
*TR: Recovery Time
The time required from the end of one measurement until completing
preparations for the next measurement. Allow at least 1 ms.
Referring to the following table, specify the prescale value
corresponding to the desired display unit
.
Na: Number of input A pulses per rotation
π
da: Circumferential length (m) of Input A per rotation
A
BCD
Encoder
To PLC
Operation Configuration (Application)
C
4
C
3
C
2
C
1
Hold
T
R
C
1
×
α
C
2
×
α
C
4
×
α
Input A
Input B
Measurement value
No measurement
Measuring period
Measuring period
Measuring period
Measuring period
Not valid
Calculated value
Display unit
Prescale value
(
α
)
Measured length
mm
1000
π
da/Na
cm
100
π
da/Na
m
π
da/Na
Summary of Contents for K35-2
Page 2: ......
Page 24: ...Outline Section 1 Outline 1 8 ...
Page 25: ...2 1 Preparations Section 2 Preparations 2 1 Mounting 2 2 2 2 Using I O 2 4 ...
Page 54: ...Basic Application Methods Basic Application Methods Section 3 Basic Application Methods 3 18 ...
Page 62: ...Initial Setup Section 4 Initial Setup 4 8 ...
Page 148: ...Functions and Operations Section 5 Functions and Operations 5 86 ...
Page 149: ...6 1 Troubleshooting Section 6 Troubleshooting 6 1 Error Displays 6 2 6 2 Countermeasures 6 3 ...
Page 152: ...Troubleshooting Section 6 Troubleshooting 6 4 ...
Page 185: ......