![Omron CVM1-CLK21 Operation Manual Download Page 75](http://html1.mh-extra.com/html/omron/cvm1-clk21/cvm1-clk21_operation-manual_742531075.webp)
59
C200HX/HG/HE Controller Link Units
Section 4-3
4-3-2
Node Addresses
Set the node addresses of each Unit on the Network using the rotary switches
on the front of the Unit. The node address is used to identify each node in the
Network can be set to any number between 01 and 32.
Set the node address using a small flat-blade screwdriver, being careful not to
damage the rotary switches.
Note
1.
Always turn OFF the PC’s power before setting the node address.
2.
Do not set the same node address twice within the same Network. An error
will occur if the same address is set for two different nodes. The ERC indi-
cator on the front of the Unit will light and either communications will stop,
or the INS indicator will not light and you will be unable to participate in the
Network.
3.
The send sequence for the data link areas is determined according to the
sequence of node addresses for automatically set data links.
4.
Assign node addresses consecutively beginning from 01 whenever possi-
ble to minimize Network construction time.
4-3-3
Baud Rates and Operating Levels
Set the following pins for the baud rate and operating level settings (DIP
switch).
Note
1.
Always turn OFF the PC’s power before setting the baud rate or operating
level.
2.
Keep pin 3 set to OFF. If it is turned ON, internal data may be erased.
Baud Rate (Pins 1 and 2)
Set the same baud rate for all the nodes on the Network using DIP switch pins
1 and 2 on the front of the Unit. The baud rate is set as shown below.
The maximum transmission distance will also change according to the setting.
Item
Specifications
Setting method
2-digit decimal
Setting range
01 to 32 (default is 01)
Node
All nodes in the Network
1's digit
10's digit
NODE NO.
X10
1
X10
0
0
1
Pin 3:
Not used (must be OFF)
Pin 4:
Operating level
Pins 1, 2: Baud rate
Note: The factory default settings are shown above.
1
SW1
ON
23
4
Pins
Baud rate
Maximum transmission
distance
Pin 1
Pin 2
OFF
OFF
2 Mbps
500 m
ON
OFF
1 Mbps
800 m
OFF
ON
500 Kbps
1 km
ON
ON
Do not set.
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......