164
Commands and Responses for C200HX/HG/HE and CQM1H-series
Section 6-6
FAL/FALS No. (response): The number of the highest priority FAL/FALS
error is returned as BCD between 00 and 99 (decimal) to the second byte.
The first byte is always 00 (Hex). If no error has occurred, 0000 (Hex) is
returned.
Error message (response): The error message of the present FAL/FALS
number is returned as 16 or fewer ASCII characters (16 or fewer bytes). If
there is no error, nothing will be returned.
6-6-12 CLOCK READ
Reads the clock.
With CQM1H-series PCs, all zeros will be returned if the CPU Unit does not
contain a Memory Cassette with a clock.
Command Block
Response Block
Parameters
Year, month, date, hour, minute, second, day (response): Each value is
expressed in BCD.
Year: The rightmost two digits of the year.
Hour: 00 to 23.
Day: As follows:
6-6-13 CLOCK WRITE
Sets the clock.
With CQM1H-series PCs, the time will not be written unless the CPU Unit
contains a Memory Cassette with a clock.
Note Be sure to specify all data.
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
0 0
0 0
0 0
0 0
Bit
1: PC link error
1: Host link error
1: Battery error
1: Remote I/O error
1: Special I/O Unit error
1: I/O verification error
1: System error (FAL)
Second byte
First byte
Command
code
01
07
01
07
Year
Date Hour Minute
Response
code
Command
code
Month
Second Day
Value
00
01
02
03
04
05
06
Day
Sun
Mon
Tues
Wed
Thur
Fri
Sat
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......