238
Status Area and Troubleshooting
Section 9-2
Data Link Status: First Data Link Status Word + 0 to + 15
Note Refer to 5-4 Checking Data Link Status for details on status flags.
Troubleshooting with Status Flags
Data Link Status
Node 2
Node 4
Node 6
Node 8
Node 10
Node 12
Node 14
Node 16
Node 18
Node 20
Node 22
Node 24
Node 26
Node 28
Node 30
Node 32
PC status
0: Inactive (user program not running)
1: Active (user program running)
Communications error (data link reception)
0: Normal
1: Error
PC's CPU Unit error
0: Normal
1: Error
Data link participation
0: Not in data link or data link inactive
1: In data link
Offset error
0: Normal
1: Error
Error: Offset exceeds
number of send words.
Insufficient (short) receive area
0: Sufficient
1: Insufficient
Insufficient: Receive
area is smaller than
send area. Excess data
is truncated; other data
is received.
Remaining receive area
0: Not remaining
1: Remaining
Remaining: Receive
area is larger than send
area. Data is received
and remaining words
are cleared.
Node 1
Node 3
Node 5
Node 7
Node 9
Node 11
Node 13
Node 15
Node 17
Node 19
Node 21
Node 23
Node 25
Node 27
Node 29
Node 31
Bit status
Probable cause
Probable remedy
PC’s CPU Unit error is 1:
ON
A fatal PC error, non-fatal
PC error, or a watchdog
timer error has occurred.
Refer to the PC’s operation
manual and correct the
error. If the error occurs
again, replace the PC.
The Unit is mounted to a
non-compatible PC.
Refer to 1-2-4 Controller
Link Unit Models and PCs
and mount onto the correct
PC.
Communications error is 1:
ON
The relevant node is not in
the Network.
Enter the node in the Net-
work.
A communications error
has occurred as a result of
noise.
Conduct an echoback test
using the Controller Link
Support Software and if
this does not correct the
error, check the usage
environment.
A communications error
has occurred.
Refer to page 218
and
troubleshoot accordingly.
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......