![Omron CVM1-CLK21 Operation Manual Download Page 71](http://html1.mh-extra.com/html/omron/cvm1-clk21/cvm1-clk21_operation-manual_742531071.webp)
55
CJ-series Controller Link Units
Section 4-2
4.
The default setting is OFF (not connected).
4-2
CJ-series Controller Link Units
The following settings are required for a Controller Link Unit used with a CJ-
series PC.
4-2-1
Overview
Unit Number
Node Address
Baud Rate
NoteFactory default setting is in bold.
Terminating Resistance
Item
Switch
Page
Unit number
Unit number setting switch
Node address
Node address switches
Baud rate
Baud rate, pins 1 and 2
Terminating resistance
Terminating resistance switch
UNIT
No.
RUN
CLK21
ERC
INS
ERH M/A LNK
RD
NODE
No.
x10
1
x10
0
01
23456789
ABCD
EF
0
TER
SD
1 2 3 45
678
9
01
2 3 45
678
9
BAUD
RATE
1
2
ON
SW1
ON
TER SW
BD H
BD L
SHLD
ON
1
2
UNIT
No.
NODE
No.
x10
1
x10
0
01
23456789
ABCD
EF
01
2 3 45
678
9
01
2 3 45
678
9
BAUD
RATE
1
2
ON
SW1
ON
1
2
Setting range
Nodes
01 to F (default is 0)
All nodes in the Network
Setting range
Nodes
01 to 32 (default is 01)
All nodes in the Network
Pins
Baud rate
Maximum
transmission
distance
Nodes
Pin 1
Pin 2
OFF OFF
2 Mbps
500 m
Set same
rate for all
nodes in the
Network.
OFF
ON
1 Mbps
800 m
ON
OFF
500 Kbps
1 km
ON
ON
Cannot be set.
Front switch
Terminating
resistance
Nodes
OFF
(factory default)
Not connected
All nodes in the Network
Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
ON
Connected
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......