47
Wired Controller Link Unit Wiring
Section 3-3
3.
Leave the tip of the wire created by twisting the shield exposed and cover
the remaining section with a heat-shrinking tube.
4.
Remove enough of the cover from the signal lines to allow the crimp termi-
nals to be connected, taking care not to damage the signal lines. Damage
to the signal lines could cause the cable to break.
5.
Twist firmly the portion of the signal lines that are exposed.
6.
Apply vinyl tape or heat-shrinking tube to the end of the cover that was
peeled in step 1.
7.
Mount the crimp terminal onto the signal lines and the shield line. Use M3
crimp terminals.
8.
Connect the signal lines and the shield line to the terminal block using the
markings on the terminal block.
Note a) You can change the length of the signal lines as shown in the fol-
lowing diagrams to make wiring a lot easier.
Wire created by
twisting the shield
Cover with a
heat-shrinking
tube
Exposed portion for
crimp terminal
connection
Apply vinyl tape or a
heat-shrinking tube.
Shield line
Communications cable
from the previous node
Communications cable
to the next node
Communications data
High signal
Communications data
Low signal
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......