165
Commands and Responses for C200HX/HG/HE and CQM1H-series PCs
Section 6-6
Command Block
Response Block
Parameters
Year, month, date, hour, minute, second, day (command): Each specified
value is expressed in BCD.
The ranges for setting these items are shown in the following table.
Day: As follows:
6-6-14 ERROR CLEAR
Clears errors from the PC. A normal response will be returned even if an error
has not occurred.
Note The cause of the error must be removed before executing the ERROR CLEAR
command or the same error will occur again after the ERROR CLEAR com-
mand is executed.
Command Block
Response Block
Parameters
Error reset code (command): Set to FFFF (Hex).
02
07
Year Month Date Hour
Command
code
Minute Second Day
02
07
Response
code
Command
code
Parameters
Range
Year
00 to 99 (rightmost 2 digits)
Month
01 to 12
Date
00 to 31
Hour
00 to 23
Minute
00 to 59
Second
00 to 59
Value
00
01
02
03
04
05
06
Day
Sun
Mon
Tues
Wed
Thur
Fri
Sat
Command
code
01
21
Error reset
code
FF
FF
Command
code
01
21
Response
code
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......