![Omron CVM1-CLK21 Operation Manual Download Page 57](http://html1.mh-extra.com/html/omron/cvm1-clk21/cvm1-clk21_operation-manual_742531057.webp)
41
Installation
Section 3-2
Installing with a PC Card Unit
When installing a Controller Link Unit along with a PC Card Unit, mount the
Controller Link Unit in the first slot on the left of the CPU Unit. Use the
C200HW-CE012 Bus Connection Unit.
3-2-2
CVM1 and CV-series PCs
Up to four Controller Link Units for CVM1 and CV-series PCs can be installed
in a CPU Backplane or a Expansion CPU Rack (including both Optical and
Wired Units). Controller Link Units cannot be installed on an Expansion I/O
Rack, a SYSMAC BUS Slave Rack, or a SYSMAC BUS/2 Slave Rack.
T
he CVM1 and CV-series Controller Link Unit is classified as a CPU Bus Unit
and must be mounted in a CPU bus slot.
Note Tighten the screws on the Backplane to a torque of 1.2 N • m.
Tighten the fixed screws on the CPU Unit to a torque of 0.9 N • m.
Controller Link Unit
PC Card Unit
CPU Unit
C200HW-CE012 Bus Connection Unit
C200HW-CLK21
Controller Link Unit
CPU Unit
(C200HE-CPU32/42-(Z)E
C200HG-CPU33/43/53/63-(Z)E
C200HX-CPU34/44/54/64-(Z)E
C200HW-COM01/04
Communications Board
C200HW-PCU01
PC Card Unit
CPU Backplane
Expansion
Backplane
2/3/5/8/10 slots
3/5/8/10 slots
CPU
Unit
Of these
slots,
installation
is possible
in up to 4
slots.
CPU Rack (CV500/CV1000/CV2000/CVM1)
The Unit can be mounted to the 3/5/10 slots
shown in the diagram on the right. (It cannot
be mounted to the leftmost slot even if an
Expansion CPU Rack is not used.)
Install in four of
these 14, 16, or
21 slots.
CPU Backplane
CV500-BC101, CVM1-BC103/CV500-BC051, CVM1-BC053/CV500-BC031
I
O
C
C
P
U
P
S
3/5/10 slots
Expansion CPU Rack
CV500/BI111
I
O
I
F
P
S
Expansion CPU Rack
Any of the 11 slots shown in the illustration
can be used. The leftmost slot cannot be
used.
I
O
I
F
P
S
Expansion I/O Rack
Controller Link Units cannot be mounted to
Expansion I/O Racks.
11 slots
PS:
Power Supply Unit
CPU: CPU
Unit
IOC:
I/O Control Unit
IOIF:
I/O Interface Unit
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......