52
CS-series Controller Link Units
Section 4-1
4-1
CS-series Controller Link Units
The following settings are required for a Controller Link Unit used with a CS-
series PC.
4-1-1
Overview
Unit Number
Node Address
Baud Rate
NoteFactory default setting is in bold.
Always leave pins 3 and 4 OFF.
Terminating Resistance
4-1-2
Unit Number
Set the unit number for each Unit using the rotary switches on the front of the
Unit. The unit number is used to identify a CPU Bus Unit within the PC. Any
unit number can be set between 0 and F in hexadecimal (00 to 15 in decimal)
.
Item
Switch
Page
Unit number
Unit number setting switch
Node address
Node address switches
Baud rate
Baud rate, pins 1 and 2
Terminating resistance
Terminating resistance switch
Setting range
Nodes
01 to F (default is 0)
All nodes in the Network
Setting range
Nodes
01 to 32 (default is 01)
All nodes in the Network
Pins
Baud rate
Maximum
transmission
distance
Nodes
Pin 1
Pin 2
OFF OFF
2 Mbps
500 m
Set same
rate for all
nodes in the
Network.
OFF
ON
1 Mbps
800 m
ON
OFF
500 Kbps
1 km
ON
ON
Cannot be set.
Front switch
Terminating
resistance
Nodes
OFF
(factory default)
Not connected
All nodes in the Network
Turn ON the terminating resis-
tance at the nodes at both
ends of the Network and turn it
OFF at all other nodes.
ON
Connected
Item
Specifications
Setting method
Single-digit hexadecimal
0
0
Note: The factory default settings are shown above.
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......