Introduction
Section 6-1
cessing is performed automatically once the number of retries has been
set, so be sure to specify a number other than “0” for the number of retries.
RECV
RECV receives “m” words beginning with S (the beginning word for data
transmission at the destination node, M) to the words from D (the beginning
word for data reception at the source node) onwards.
Note
1.
When communicating in the same network with CVM1 and CV-series PCs
manufactured prior to April 1996, the local network address cannot be set
to “00.” Set a number other than “00” as the local network address in the
routing tables, and then specify that number.
Direct/Indirect
0: Direct; 1: Indirect
S: Destination node beginning send word
D: Source node beginning receive word
C: Source node first control data word
Destination node M
Source node
C + 2
@RECV(98)
S
D
C
C
"m" number of send words
0000 to 03DE (Hex): 0 to 990 words
C + 1 1
Always "1" for Controller
Link Networks
Always "1" for Controller Link Networks
0: Response required
1: Response not required
Destination (transmission source) node address (M)
00 to 20 (Hex): 0 to 32
The range of node addresses will vary for networks
other than Controller Link Networks.
0: Source network address not specified (local network)
1: Source network address specified.
Response monitor time
00 (Hex): 2 s (for 2 Mbps)
4 s (for 1 Mbps)
8 s (for 500 Kbps)
01 to FE (Hex):
FF (Hex): No response monitoring
Destination (transmission source) unit address
00 (Hex):
PC's CPU Unit
01 (Hex):
Computer (user program)
10 to 1F (Hex):
Unit Nos. 0 to 15
FE (Hex):
Unit connected to network
C + 3
0
0
Destination network address
00 (Hex):
Local network
01 to 7F (Hex):
1 to 127
This setting is enabled only when "Destination network address specified" is set in word C.
When specifying the destination network address, set all the nodes in the routing tables. For
details on the routing tables, refer to
1514
0
1514
131211
8 7
0
8 7
15
0
15
0
Number of retries
0 to F (Hex): 0 to 15 retries
"m" num-
ber of
send
words
D
15
0
15
0
m
S
…
1
…
0.1 to 25.4 s (unit: 0.1 s)
Section 7 Network Interconnections.
Summary of Contents for CVM1-CLK21
Page 2: ......
Page 3: ......
Page 4: ...iv...
Page 6: ...vi...
Page 33: ...17 Application Precautions Section 1 5 2 9 8 2 2 8 5 2...
Page 34: ......
Page 42: ......
Page 66: ......
Page 103: ...87 Setting Data Links Section 5 2 Device Information Setting Data Link Tables...
Page 124: ......
Page 192: ......
Page 280: ......
Page 284: ......
Page 300: ......
Page 304: ......