Section 4-6
$&*
For every Output the assigned External Interrupt Task number can be calculated
with the following formula (‘O’ = Output):
Assigned External Interrupt Task Number to the
•
rising edge of the Output bit is equal to: 2xO
•
falling edge of the Output bit is equal to: 2xO+1
For a complete overview of all External Interrupt Task numbers to be assigned to
the Outputs, refer to Appendix
"Assigning External Interrupt Tasks to Outputs".
Since there are 256 External Interrupt Tasks available (numbered 0 to 255) the
Offset can be maximum 192. With an Offset of 192 the last Output (31) will be
assigned the last available External Interrupt Task 255 (=192+2x31+1).
Example 1
If you only want Digital Output 3 to generate interrupts and you only want to exe-
cute an External Interrupt Task on the rising edge of Digital Output 3, than you
must enable Output 3 to generate interrupts (m+2 = 0008
H
and m+3 = 0000
H
). If
you decide to use an Offset of 5 (m+1 = 0005
(BCD)
) than External Interrupt Tasks 11
and 12 will be assigned to Output 3. In External Interrupt Task 11 you should write
an appropriate (ladder) program which is to be executed at a rising edge of the
corresponding bit of Output 3 in the Unit Output Pattern. External Interrupt Task 12
must also be programmed but will remain empty since no action is required on a
falling edge of Output 3.
Example 2
An Offset of 10 (m+1 = 0010
(BCD)
), with all 32 Outputs enabled to generate inter-
rupts (m+2 and m+3 = FFFF
H
), means that the rising edge of the corresponding
bit of Output 0 in the Unit Output Pattern is assigned to External Interrupt Task
Number 10 and the falling edge to External Interrupt Task 11. The rising edge of
Output 1 to External Interrupt Task Number 12 and the falling edge to External
Interrupt Task Number 13 and so on. For Output 31 the two External Interrupt
Tasks 72 and 73 are assigned. Now you have External Interrupt Tasks 10 to 73
available. In every Task you should write an appropriate (ladder) program which is
to be executed at the Outputs’ corresponding rising or falling edge.
The application example in section 6-4
“CAM-positioning”
shows you how to use
outputs generating interrupts.
General Setting:
m+1
Interrupt Task Offset (Outputs):
Set between 000 - 192
(BCD)
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
W902-E2-03.book Seite 137 Donnerstag, 7. Oktober 2004 2:06 14
Summary of Contents for CS1W-CT021
Page 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Page 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Page 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Page 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Page 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Page 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Page 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...