Section 5-3
$(-
Inspection Equipment
Prepare the following equipment before inspecting the system.
Required Equipment:
Have a standard and Phillips-head screwdriver, multimeter, alcohol, and a clean
cloth.
Equipment that could be needed:
Depending on the system conditions, a synchroscope, oscilloscope, thermometer,
gas sensor or hygrometer (to measure humidity) might be needed.
Inspection Procedure
Check the items in the following table and correct any items that are not according
to the criteria.
Item
Criteria
Equipment
Environmental
conditions
Ambient temperature
0
°
C to 55
°
C
Thermometer
Ambient humidity
10% to 90%
Hygrometer
Dust/dirt accumulation
None
---
Is the Unit exposed to any spray
of water, oil, or chemicals?
None
---
Is the Unit exposed to corrosive
or flammable gases?
None
Gas sensor
Is the Unit exposed to shock or
vibration?
None
Installation
Is the Unit installed securely?
No looseness ---
Are the external connectors
securely mounted?
No looseness ---
Is all external wiring securely
connected?
No looseness ---
Are the external connectors
fully inserted?
No looseness ---
Are the connecting cables
undamaged?
No damage
---
W902-E2-03.book Seite 150 Donnerstag, 7. Oktober 2004 2:06 14
Summary of Contents for CS1W-CT021
Page 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Page 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Page 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Page 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Page 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Page 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Page 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...