Section 5-3
$',
5-2-6
System Errors
When errors occur in the CS1-CPU Unit or on the I/O Bus the ERH-LED is turned
ON. At the occurrence of an I/O Bus error an error code (see n+17, n+18) is gen-
erated as well.
Clearing System errors
Turn ON the power supply again or restart the system. If the error persists then
replace the CS1-CPU.
5-3
Maintenance and Inspection
This section describes the routine cleaning and inspection recommended as reg-
ular maintenance.
5-3-1
Cleaning
Clean the High-speed Counter Unit regularly as described below in order to keep
it in its optimal operating condition.
•
Wipe the Unit with a dry, soft cloth for regular cleaning.
•
When a spot cannot be removed with a dry cloth, dampen the cloth with a neu-
tral cleanser, wring out the cloth, and wipe the Unit.
•
A smudge may retain on the Unit from gum, vinyl, or tape that was left on for a
long time. Remove the smudge when cleaning.
!Caution
Never use volatile solvents such as paint thinner or benzene or chemical wipes.
These substances could damage the surface of the Unit.
5-3-2
Routine Inspections
In order for your High-speed Counter Unit to continue operating at optimum con-
dition, periodic inspections are necessary. Be sure to inspect the system periodi-
cally to keep it in its optimal operating condition. In general, inspect the system
once every 6 to 12 months, but inspect more frequently if the system is used with
high temperature or humidity or under dirty / dusty conditions.
Error Code 1
Error Code 2
Error
Description
000E
0000
I/O Bus error
An error has occurred on the I/O Bus causing
the High-speed Counter Unit to be in an
undefined state. On occurrence of an I/O Bus
error you can configure the Outputs to keep
their last state or to have a predefined state
(refer to 3-5-4
"Output Control Configuration"
).
0002
Time-Out in
milliseconds
Time-Out error
A cyclic refresh time-out error was generated
caused by a PLC system error or you have
chosen to disable the Cyclic Refresh of the
High-speed Counter Unit in the CS1-PLC
settings. This error will be cleared as soon as
Cyclic Refresh will take place again.
W902-E2-03.book Seite 149 Donnerstag, 7. Oktober 2004 2:06 14
Summary of Contents for CS1W-CT021
Page 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Page 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Page 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Page 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Page 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Page 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Page 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...