0)>4%"(+)*-?('5-0LMMNI0CMLO
Appendix A
Item
C200H-CT021
CS1W-CT021/CT041
Counting
Range
BCD:
-8,388,608 to +8,388,607
Hexadecimal:
800000 to FFFFFF (-8,388,606 to –1) and
000000 to 7FFFFF (0 to 8,388,607)
Hexadecimal:
Circular Counter: 00000000 to FFFFFFFF (0 to
4,294,967,295)
Linear and Simple Counter: 80000000 to
7FFFFFFF (-2,147,483,648 to +2,147,483,647)
Number of
Counters
2
2 (CS1W-CT021), 4 (CS1W-CT041)
Signals per
Counter
Phase A, B and Z
Phase A, B and Z
Count Signal
Levels
Line Driver
24 VDC
Line Driver
5, 12 and 24 VDC
Input Signal
Types
Phase Differential (multiplication x1, x2, x4)
Up and Down
Pulse and Direction
Phase Differential (multiplication x1, x2, x4)
Up and Down
Pulse and Direction
Machine
Number
Setting
0 to 15 (selectable by one rotary switch)
0 to 92 (selectable by two rotary switches)
Number of
slots
1 Slot,
10 words in IR-area (IR100 to IR 199 or IR
400 to IR459
100 words in DM-area (DM1000 to DM 2599)
4 Slots,
40 words in CIO-area (CIO 2000 to CIO 2959)
400 words in DM-area (DM 20000 to DM 29599)
Applicable
PLC’s
C200H, C200HS, C200HX, C200HG,
C200HE, CS1
CS1
Current
Consumption
400 mA at 5 VDC (Supplied from Backplane) 450 mA (CS1W-CT041), 360 mA (CS1W-CT021)
(at 5V via backplane)
Digital
Outputs
16 Outputs consisting of:
8 (external) Digital Outputs (NPN/PNP
selectable by DIP-switch)
8 Soft Outputs
Maximum switching capacity 16 to 80 mA at
5V to 24 VDC
32 Outputs consisting of:
4 (external) Digital Outputs (NPN/PNP selectable
in DM)
28 Soft Outputs
Maximum switching capacity 46 to 100 mA at 12
to 24 VDC
Digital Inputs
4 (i.e. 2 per Counter)
Input Voltage 12 and 24 VDC
4 (can be assigned to multiple Counters, allowing
one Counter to be controlled by a maximum of 4
Digital Inputs)
Input Voltage 24 VDC
Maximum
Input
Frequency
75 kHz
500 kHz
Response
time
BCD: 1.2 ms max
Hexadecimal: 1.0 ms max
0.5 ms max
Output
Control Mode
Unit is per default in Range Mode and
Outputs are controlled according to the
Counter Value being within Range Limits
(Comparison Mode is not available)
Unit can be configured for Range Mode or
Comparison Mode. In Comparison Mode the
Outputs are controlled according to the direction
in which the Counter Value crosses a
Comparison Value
Digital Input
Functionality
Digital Inputs can not be configured to have
different functionality
Every Digital Input can be configured according
to one out of 17 available functions
W902-E2-03.book Seite 173 Donnerstag, 7. Oktober 2004 2:06 14
Summary of Contents for CS1W-CT021
Page 1: ...OPERATION MANUAL High speed Counter Units CS1W CT021 CS1W CT041 Cat No W902 E2 03...
Page 3: ...W902 E2 03 book Seite iv Donnerstag 7 Oktober 2004 2 06 14...
Page 5: ...W902 E2 03 book Seite vi Donnerstag 7 Oktober 2004 2 06 14...
Page 39: ...W902 E2 03 book Seite 24 Donnerstag 7 Oktober 2004 2 06 14...
Page 59: ...A 2 Section 2 3 W902 E2 03 book Seite 44 Donnerstag 7 Oktober 2004 2 06 14...
Page 155: ...4 Section 4 6 W902 E2 03 book Seite 140 Donnerstag 7 Oktober 2004 2 06 14...
Page 199: ...G W902 E2 03 book Seite 184 Donnerstag 7 Oktober 2004 2 06 14...