5 Message Communications
5 - 14
CompoNet Communications Unit User’s Manual (I582-E1)
5-5
Parameter Read/Write (Class 65 hex)
Function Code Object (Class 65 hex) - Supported Service Codes
Use each inverter parameter number as a Function Code in the Instance and Attribute objects.
A Function Code is calculated using a sequence number of the parameter function group (A = 0, B = 1,
etc) x 1000 + the 3-digit parameter number. This Function Code is used to allocate the Instance (2 high
bytes) and Attribute (2 low bytes).
Function Code Object (Class0x65) - Supported Instance and Attribute Codes
Precautions for Correct Use
Precautions for Correct Use
• For details about Modbus registers and data sizes, refer to
Section 6-8 Modbus Communication (Modbus-RTU) Data List of the MX2 User's Manual
(Cat. No. I570) and 8-5 Modbus Communication Register Number List of the RX User's Manual (Cat.
No. I578).
• All data written by the Function Code object are saved temporary in the inverter memory. Be sure to
execute the ENTER command at the end of the writing sequence to store the values in EEPROM.
• Function Code F001 cannot be written using the Function Code object.
• Parameter b127 takes double-word data, which is different from the data size of Modbus registers
(single word).
• The ENTER command is executed by the following object and written to EEPROM. Refer to
Saving Changes to Holding Registers (ENTER Command)
Write to EEPROM: Class 65 hex, Instance 09 hex, Attribute 00 (0900 hex)
5-5-1
Supported Service Codes
Service Code No. (hex)
Service Description
0E
Reads Attribute data.
10
Writes Attribute data.
5-5-2
Supported Instance and Attribute Codes
Function Code
Decimal Base
Decimal Range
hexadecimal Range
A001 to A999
0
1 - 999
0001 to 03E7
b001 to b999
1000
1000 - 1999
03E9 to 07CF
C001 to C999
2000
2001 - 2999
07D1 to 0BB7
d001 to d999
3000
3001 - 3999
0BB9 to 0F9F
F001 to F999
5000
5001 - 5999
1389 to 176F
H001 to H999
7000
7001 - 7999
1B59 to 1F3F
P001 to P999
15000
15001 - 15999
3A99 to 3E7F
U001 to U999
20000
20001 - 20999
4E21 to 5207
Summary of Contents for 3G3AX-MX2-CRT-E
Page 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Page 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Page 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Page 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Page 171: ......