4 Remote I/O
4 - 6
CompoNet Communications Unit User’s Manual (I582-E1)
Input Format (CS/CJ-series
←
Inverter)
Input Bit/Data Details
Standard Remote Input Assembly ID: 71 Dec (47 hex)
Word
No.
Byte
No.
Bit Allocation
bit 7
bit 6
bit 5
bit 4
bit 3
bit 2
bit 1
bit 0
n
0
FA1
RFN
CFN
IRDY
RVR
FWR
WR
AL
1
Drive Status
n + 1
2
Rotation Speed Monitor (Low byte)
3
Rotation Speed Monitor (High byte)
Name
Description
AL
Alarm output
0: Normal
1: Fault/Trip
WR
Warning
0: Normal
1: Warning
FWR
During forward
operation
0: During reverse run/Stopping
1: During forward run
RVR
During reverse
operation
0: During forward run/Stopping
1: During reverse run
IRDY
Operation ready
0: Not ready
1: Ready
CFN
Ctrl. from Net
0: Follow the setting of parameter A002.
1: CompoNet reference
RFN
Ref. from Net
0: Follow the setting of parameter A001.
1: CompoNet reference
FA1
Constant speed
reached
0: Accelerating or decelerating/Stopping
1: Frequency agree
Drive State Detail
1: Startup
2: Not ready
3: Ready
4: Operation in progress
5: Stopping
6: Fault/Trip stop
7: Fault/Trip
Rotation Speed Monitor
If parameter P049 (Number of Poles for Rotation Speed Setting) is set appropri-
ately, the rotational speed unit is [min
-1
].
If parameter P049 (Number of Poles for Rotation Speed Setting) is set to 0, the
frequency is monitored in units of [0.01 Hz].
Summary of Contents for 3G3AX-MX2-CRT-E
Page 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Page 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Page 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Page 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Page 171: ......