![background image](http://html1.mh-extra.com/html/omron/3g3ax-mx2-crt-e/3g3ax-mx2-crt-e_user-manual_740779156.webp)
Appendices
A - 6
CompoNet Communications Unit User’s Manual (I582-E1)
Additional Information
• The data to be allocated to each assembly in this object is the same as that defined in
Table A-8 Connection Object - Object Details
A-1-4
Connection Object (Class 05 hex)
Supported Service Codes
Table A-7 Connection Object - Supported Service Codes
Service Code No. (hex)
Service Description
0E
Reads Attribute data.
10
Writes Attribute data.
Object Details
Instance
(hex)
Attribute
(hex)
Name
Description
Setting
Range
Default
Read Write
Size
01
Multicast
Poll I/O
01
State
Status of the instance
----
1
Yes
No
USINT
02
Instance
Type
Type of the instance
----
1
Yes
No
USINT
03
Transport
Class Trig-
ger
Defines the communications
type by code.
----
83 hex
Yes
No
byte
07
Produced
Connection
Size
Indicates the maximum num-
ber of bytes for transmission.
----
16
Yes
No
UINT
08
Consumed
Connection
Size
Indicates the maximum num-
ber of bytes for reception.
----
16
Yes
No
UINT
09
Expected
Packet
Rate
Indicates the length of the
internal processing timeout
when a communications
request is received (in units of
10 ms).
0-
65535
0
Yes
Yes
UINT
0C
Watchdog
Time-out
Action
Indicates the action for the
internal processing timeout
related to communications.
00: Retain timeout status
(until reset or cleared)
01: Update connection auto-
matically
02: Operate with the same
connection
----
0
Yes
Yes
USINT
Summary of Contents for 3G3AX-MX2-CRT-E
Page 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Page 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Page 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Page 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Page 171: ......