![background image](http://html1.mh-extra.com/html/omron/3g3ax-mx2-crt-e/3g3ax-mx2-crt-e_user-manual_740779164.webp)
Appendices
A - 14
CompoNet Communications Unit User’s Manual (I582-E1)
Table A-21 Error Code Conversion
Error/Trip Code
CIP Fault/Warning Code
Code
Name
Code
Name
E01
Overcurrent protection at constant speed
2200
Current inside device
E02
Overcurrent protection during deceleration
2214
Overcurrent during slowdown
E03
Overcurrent protection during acceleration
2213
Overcurrent during startup
E04
Other overcurrent protection
2200
Current inside device
E05
Overload protection
2220
Continuous overcurrent
E06
Braking resistor overload protection
7112
Brake chopper overcurrent
E07
Overvoltage protection
3210
Overvoltage inside device
E08
EEPROM error
6320
Parameter error
E09
Undervoltage
3220
Undervoltage inside device
E10
Current detector error
5210
Measurement circuit
E11
CPU error
6100
Internal software
E12
External trip
9000
External malfunction
E13
USP error
9000
External malfunction
E14
Ground fault
2120
Short to ground
E15
Input overvoltage protection
3110
Trunk line overvoltage
E16
Momentary power interruption protection
3120
Trunk line undervoltage
E20
Temperature error due to cooling fan frequency low-
ering
4000
Temperature
E21
Temperature error
4200
Device temperature
E22
CPU error
5000
Device hardware
E24
Phase failure
3130
Phase failure
E25
Main circuit error
5410
Output stages
E30
Driver error
5400
Power section
E35
Thermistor error
7300
Sensor
E36
Braking error
9000
External malfunction
E37
Emergency disconnect
9000
External malfunction
E38
Low-speed overload protection
2221
Continuous overcurrent 1
E40
Operator connection error
5300
Operator control circuit
E41
Modbus communication error
7500
Communications
E60
Option error (Inverter communications error)
7510
Serial interface 1
E61
Option error (Duplicated MAC ID)
7510
Serial interface 1
E62
Option error (External trip)
7510
Serial interface 1
E63
DRT/CRT Communication lost / idle
7510
Serial interface 1
E64
Illegal flexible mapping
6320
Parameter error
E65
Option error (Reserved)
7510
Serial interface 1
E66
Option error (Reserved)
7510
Serial interface 1
E67
Option error (Reserved)
7510
Serial interface 1
E68
Option error (Reserved)
7510
Serial interface 1
E69
Option error (Inverter communications lost error)
7510
Serial interface 1
E70
Option error (Inverter communications error)
7510
Serial interface 2
E71
Option error (Duplicated MAC ID)
7510
Serial interface 2
E72
Option error (External trip)
7510
Serial interface 2
E73
DRT/CRT communications lost/idle
7510
Serial interface 2
E74
Illegal flexible mapping
6320
Parameter error
E75
Option error (Reserved)
7510
Serial interface 2
E76
Option error (Reserved)
7510
Serial interface 2
E77
Option error (Reserved)
7510
Serial interface 2
E78
Option error (Reserved)
7510
Serial interface 2
E79
Option error (Inverter communications lost error)
7510
Serial interface 2
E80
Encoder disconnection
7305
Incremental encoder 1 defective
Summary of Contents for 3G3AX-MX2-CRT-E
Page 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Page 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Page 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Page 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Page 171: ......