![background image](http://html1.mh-extra.com/html/omron/3g3ax-mx2-crt-e/3g3ax-mx2-crt-e_user-manual_740779166.webp)
Appendices
A - 16
CompoNet Communications Unit User’s Manual (I582-E1)
01
11
Output Voltage
Output voltage monitor
Unit: [V]
----
----
Yes
No
INT
12
Accel Time
Unit: [ms]
10 -
3600000
10000
Yes
Yes
UINT
13
Decel Time
Unit: [ms]
10 -
3600000
10000
Yes
Yes
UINT
1D
Reference From
the Net
Speed reference input selec-
tion monitor:
0: Follow the setting of param-
eter A002.
1: CompoNet
0 - 1
0
Yes
Yes
BOOL
77
Torque Actual
Rel
Actual torque monitor
Unit: [%]
----
----
Yes
Yes
INT
78
Torque Ref Rel
Reference torque: Unit: [%]
0 - 200
0
Yes
Yes
INT
79
Torque Com-
pensation Bias
Rel
Compensation bias torque
Unit: [%]
-200 -
200
0
Yes
Yes
INT
7A
At Zero Speed
0: Non-zero speed
1: At zero speed
----
----
Yes
No
BOOL
Instance
(hex)
Attribute
(hex)
Name
Description
Setting
Range
Default
Read Write
Size
Summary of Contents for 3G3AX-MX2-CRT-E
Page 94: ...3 Network Startup 3 36 CompoNet Communications Unit User s Manual I582 E1...
Page 118: ...4 Remote I O 4 24 CompoNet Communications Unit User s Manual I582 E1...
Page 134: ...5 Message Communications 5 16 CompoNet Communications Unit User s Manual I582 E1...
Page 167: ...I 1 I CompoNet Communications Unit User s Manual I582 E1 Index...
Page 171: ......