7.3.3.4
Alternate Timescale pane (only available for profiles
Power (C37.238-2011) and Power (C37.238-2017))
This pane is only available for the PTP profiles Power (C37.238-2011) and Power (C37.238-2017)
supported by
OTMC 100p
.
Display name
Use this field to specify the designation of the alternate timescale
(ALTERNATE_TIME_OFFSET_INDICATOR TLV). Text of max. 10 characters.
See "displayname" and "ALTERNATE_TIME_OFFSET_INDICATOR" in
IEEE 1588-2008 (clause 16.3.3.7) and IEEE C37.238.
Current offset
Use this field to specify the value for the
ALTERNATE_TIME_OFFSET_INDICATOR TLV. This is the offset (in seconds) of
the alternate time from the node time. The alternate time is the sum of this value
and the node time. See "ALTERNATE_TIME_OFFSET_INDICATOR" in
IEEE 1588-2008 (clause 16.3.3.4) and IEEE C37.238.