4-12
IMSBR08-E2
4.4 Setting Commands
p 6
Relay output
O N
Relay ON
O F F
Relay OFF
p 7
Relay number (
µ
R10000: I01 to I06, SBR-EW180
: I01 to I06, I11 to I16, I21 to I26, I31 to I36)
Query
S A [ p 1 [ , p 2 ] ] ?
Example
Set a high limit alarm (alarm value = 1000) on alarm
number 1 of channel 02 and output to relay I01.
S A 0 2 , 1 , O N , H , 1 0 0 0 , O N , I 0 1
Description • When the input range is set to SKIP (SR command),
p3 cannot be turned ON.
• The alarm settings are all turned OFF for the
following cases.
• When the input type is changed (VOLT, TC,
etc).
• When the range type is changed.
• When the span and scaling values are changed
during linear scaling (includes changing the
decimal position).
• The h and l settings of p4 are valid only when the
measurement range is set to computation between
channels.
• The hysteresis of alarm ON/OFF (valid when p4 is
H or L) is set using the XA command.
• If p4 is set to R or r, set the interval for the high/low
limit on the rate-of-change using the XA command.
• The T and t settings of p4 can be specified when
the alarm delay function is enabled (UF command).
• If p4 is set to T or t, set the alarm delay time for the
delay high/low limit alarm using the BD command.
• Parameter p5 for the high limit alarm/low limit alarm
and delay high limit alarm/delay lowlimit alarm
• For DC voltage, TC, and RTD input: Values
within the measurable range in the specified
range (example: –2.000 to 2.000 V for the 2 V
range).
• For ON/OFF input (DI): 0 or 1.
• For scaling (1-5V, scaling, and square root):
−
5
to 105% of the scale span (except within
−
20000
to 30000).
• Parameter p5 for the difference high limit alarm/
difference low limit alarm: Values in the measurable
range can be specified (example: –1760.0 to
1760.0
⋅
C for the TC type R).
• Parameter p5 for the high limit on rate-of-change
alarm/low limit on rate-of-change alarm: A value
greater than or equal to 1 digit can be specified.
For example, 1 digit corresponds 0.001 for the 2 V
range (measurable range: –2.000 to 2.000 V). The
maximum value that can be specified is the width
of the measurable range (4.000 V for 2 V range).
For ON/OFF input, only “1” can be specified.
• On models with the computation function (/M1
option), alarms can be set on computation
channels.
• When the computation equation setting (SO
command) is turned OFF, p3 cannot be turned
ON.
• For computation channels, the alarm types that
can be specified are H (high limit alarm), L (low
limit alarm), T (delay high limit alarm), and t
(delay low limit alarm). T and t can be specified
when the alarm delay function is enabled (UF
command).
• If p4 is set to T or t, set the alarm delay time for
the delay high/low limit alarm using the BD
command.
• Set p5 within the range –9999999 to 99999999
excluding the decimal using an integer.
• The alarm ON/OFF hysteresis is set using the
XA command.
• If the computation channel ON/OFF state, the
computing equation, or the span value is
changed, all alarm settings of that channel are
turned OFF.
SN
Sets the unit.
Syntax
S N p 1 , p 2
<terminator>
p 1
Channel number
p 2
Unit string (up to 6 characters)
Query
S N [ p 1 ] ?
Example
Set the unit of channel 02 to M/H.
S N 0 2 , M / H
Description • The unit setting is valid on channels set to 1-5V,
scaling, or square root.
• For the characters that can be used for the units,
see appendix 1, “ASCII Character Codes.”
• On models with the computation function (/M1
option), unit can be set on computation channels.
SC
Sets the chart speed.
Syntax
S C p 1
<terminator>
p 1
Chart speed
Query
S C ?
Example
Set the chart speed to 25 mm/h.
S C 2 5
Description Select the chart speed from the list of choices below.
Pen model
5 to 12000 mm/h (82 levels, see section 4.3)
Dot model
1 to 1500 mm/h (1 mm steps)