4-11
IMSBR08-E2
Commands
4
Description • This command cannot be specified while
computation is in progress.
• Set p4 according to the table in section 4.3.
• For p5 and p6, enter an integer value of 5 digits or
less according to the table in section 4.3. The
decimal position is fixed to the position indicated in
the table in section 4.3.
• Be sure that p8 is greater than p7.
When setting the square root
Syntax
S R
p 1 , p 2 , p 3 , p 4 , p 5 , p 6 , p 7 , p 8 , p 9 , p 1 0
<terminator>
p 1
Channel number
p 2
Measurement mode (SQRT)
p 3
Range type
p 4
Leftmost value of span
p 5
Rightmost value of span
p 6
Leftmost value of scaling (
−
20000 to 30000)
p 7
Rightmost value of scaling (
−
20000 to 30000)
p 8
Scaling decimal point position (0 to 4)
p 9
Low-cut function (ON, OFF)
p 1 0
Low-cut value
Query
S R [ p 1 ] ?
Example
Given channel 01 whose input range is 0 to 10 V, take
the square root of the input value and scale the result
in the range 0.00 (m
3
/s) to 100.00 (m
3
/s). When the
input value is less than or equal to 5.0% of the
recording span, use the low-cut function.
S R
0 1 , S Q R T , 2 0 V , 0 , 1 0 0 0 , 0 , 1 0 0 0 0 , 2 , O N ,
5 0
Description • This command cannot be specified while
computation is in progress.
• Set p3 according to the table in section 4.3.
• For p4 and p5, enter an integer value of 5 digits or
less according to the table in section 4.3. The
decimal position is fixed to the position indicated in
the table in section 4.3.
• Be sure that p7 is greater than p6.
• Parameters p9 and p10 is valid only when the low-
cut function is enabled (see the UF command).
SO
Sets the computing
equation
(/M1 option).
Syntax
S O p 1 , p 2 , p 3 , p 4 , p 5 , p 6
<terminator>
p 1
Computation channel number
p 2
Turn ON/OFF the computing equation (ON, OFF)
p 3
Computing equation (up to 120 characters)
p 4
Leftmost value of span (
−
9999999 to 99999999)
p 5
Rightmost value of span (
−
9999999 to 99999999)
p 6
Span decimal point position (0 to 4)
Query
S O [ p 1 ] ?
Example
Calculate the sum of channel 01 and 02 on
computation channel 0A. Set the leftmost and
rightmost values of span to –10.00 and 15.00,
respectively.
S O 0 A , O N , 0 1 + 0 2 ,
−
1 0 0 0 , 1 5 0 0 , 2
Description • This command cannot be specified while
computation is in progress.
• For a description on the computing equations, see
the
µ
R10000 Recorder User’s Manual
.
• For p4 and p5, enter a value using 7 digits or less
,excluding the decimal, for negative numbers and 8
digits or less for positive numbers.
VB
Sets the bias.
Syntax
V B p 1 , p 2 , p 3
<terminator>
p 1
Channel number
p 2
Bias ON/OFF (ON, OFF)
p 3
Bias value
Query
V B [ p 1 ] ?
Example
Given channel 03 whose range type is 2V
(measurable range:
−
2.000 to 2.000 V), add a bias of
0.1 V.
V B 0 3 , O N , 1 0 0
Description • Set p3 in the range of ±10% of the span of the
measurable range at the range type or ±10% of the
scaling span. Specify the value with an integer
(see section 4.3).
• The bias setting is valid only when the bias
function is enabled (see the UF command).
SA
Sets the alarm.
When not using the alarm
Syntax
S A p 1 , p 2 , p 3
<terminator>
p 1
Channel number
p 2
Alarm number (1 to 4)
p 3
Alarm ON/OFF state (OFF)
Query
S A [ p 1 [ , p 2 ] ] ?
Example
Do not use alarm number 4 of channel 01.
S A 0 1 , 4 , O F F
When using the alarm
Syntax
S A
p 1 , p 2 , p 3 , p 4 , p 5 , p 6 , p 7
<terminator>
p 1
Channel number
p 2
Alarm number (1 to 4)
p 3
Alarm ON/OFF state (ON)
p 4
Alarm type
H
High limit alarm
L
Low limit alarm
h
Difference high limit alarm
l
Difference low limit alarm
R
High limit on rate-of-change alarm
r
Low limit on rate-of-change alarm
T
Delay high limit alarm
t
Delay low limit alarm
(Characters are case-sensitive.)
p 5
Alarm value
4.4 Setting Commands