![background image](http://html1.mh-extra.com/html/omega/sbr-ew100/sbr-ew100_user-manual_4033456078.webp)
5-7
IMSBR08-E2
5
Responses
Decimal Point Position/Unit Information
• The FE command (FE1) is used to output the data.
• Syntax
The data is output for each channel in the following syntax.
E A C R L F
s_kccuuuuuu,ppCRLF
••••••••••••••••••
E N C R L F
s
Data status (N, D, S)
N
: Normal
D
: Differential input
S
: Skip (When the input range is set to SKIP for a measurement
channel or when the channel is turned OFF for a computation
channel)
k
Channel type
0
: Measurement channel
A
: Computation channel
c c
Channel number
SBR-EW100: 01 to 06, 0A to 0P
SBR-EW180: 01 to 24, 0A to 1P
u u u u u u
Unit information (6 characters, left-justified)
mV____
: mV
V_____
: V
^C____
:
°
C
xxxxxx
: (User-defined character string)
p p
Decimal point position (00 to 04)
No decimal (00000) for 00.
One digit to the right of the decimal (0000.0) for 01.
Two digits to the right of the decimal (000.00) for 02.
Three digits to the right of the decimal (00.000) for 03.
Four digits to the right of the decimal (0.0000) for 04.
_
Space
• Example
E A
N 001mV ,01
N 002mV ,01
E N
5.2 Output Format of ASCII Data