4-14
IMSBR08-E2
4.4 Setting Commands
ST
Sets the tag.
Syntax
S T p 1 , p 2
<terminator>
p 1
Channel number
p 2
Tag string (up to 7 characters)
Query
S T [ p 1 ] ?
Example
Set the tag of channel 02 to TI-2.
S T 0 2 , T I - 2
Description • For the characters that can be used for the tags,
see appendix 1, “ASCII Character Codes.”
• On models with the computation function (/M1
option), computation channels can be specified.
SG
Sets the message.
Syntax
S G p 1 , p 2
<terminator>
p 1
Message number (1 to 5)
p 2
Message string (up to 16 characters)
Query
S G [ p 1 ] ?
Example
Set character string “START” in message number 1.
S G 1 , S T A R T
Description For the characters that can be used for the messages,
see appendix 1, “ASCII Character Codes.”
SE
Sets the secondary chart
speed (used by the remote
control function (/R1
option)).
Syntax
S E p 1
<terminator>
p 1
Secondary chart speed
See the explanation.
Query
S E ?
Example
Set the chart speed to 50 mm/h.
S E 5 0
Description Select the chart speed from the list of choices below.
Pen model
5 to 12000 mm/h (82 levels, see section 4.3)
Dot model
1 to 1500 mm/h (1 mm steps)
SV
Sets the moving average
(dot model).
Syntax
S V p 1 , p 2
<terminator>
p 1
Channel number
p 2
Number of samples for computing the moving
average (OFF, 2 to 16) [times]
Query
S V [ p 1 ] ?
Example
Set the number of samples for computing the moving
average of channel 02 to 12.
S V 0 2 , 1 2
Description • This setting is available on the dot model.
• This setting is possible when moving average is
enabled (UI command).
SF
Sets the input filter (pen
model).
Syntax
S F p 1 , p 2
<terminator>
p 1
Channel number
p 2
Filter time constant (OFF, 2s, 5s, 10s)
Query
S F [ p 1 ] ?
Example
Set the filter of channel 02 to 2 s.
S F 0 2 , 2 s
Description This setting is possible when the input filter is enabled
(UJ command).
BD
Sets the alarm delay time.
Syntax
B D p 1 , p 2
<terminator>
p 1
Channel number
p 2
Alarm delay (1 to 3600) [s]
Query
B D [ p 1 ] ?
Example
Set the alarm delay of channel 01 to 120 s.
B D 0 1 , 1 2 0
Description • This setting is possible when the alarm delay
function is enabled (UF command).
• On models with the computation function (/M1
option), computation channels can be specified.
VF
Sets the brightness of the
display (VFD) and internal
illumination.
Syntax
V F p 1 , p 2
<terminator>
p 1
VFD brightness (1 to 8)
p 2
Internal illumination (OFF, 1 to 4)
O F F
Turns OFF the internal illumination.
Query
V F ?
Example
Set the display (VFD) brightness to 2 and the internal
illumination to 1.
V F 2 , 1
Description The brightness increases as the value increases.
TD
Sets the DST.
Syntax
T D
p 1 , p 2 , p 3 , p 4 , p 5 , p 6 , p 7 , p 8 , p 9
<terminator>
p 1
Use/Not use DST (USE, NOT)
p 2
DST start time: month (Jan, Feb, Mar, Apr, May,
Jun, Jul, Aug, Sep, Oct, Nov, or Dec)
p 3
DST start time: number of the week in the month
(1st, 2nd, 3rd, 4th, or Last)
p 4
DST start time: day of the week (Sun, Mon, Tue,
Wed, Thu, Fri, or Sat)
p 5
DST start time: hour (0 to 23)
p 6
DST end time: month (Jan, Feb, Mar, Apr, May,
Jun, Jul, Aug, Sep, Oct, Nov, or Dec)
p 7
DST end time: number of the week in the month
(1st, 2nd, 3rd, 4th, or Last)
p 8
DST end time: day of the week (Sun, Mon, Tue,
Wed, Thu, Fri, or Sat)
p 9
DST end time: hour (0 to 23)
Query
T D [ p 1 ] ?